Installation
and
Operation
Manual
2
Agency
Listings,
Approvals
Underwriters
Laboratories
(UL/ULC)
Requirements
for
All
Installations
The
general
requirements
are
described
in
this
section.
When
installing
an
individual
device,
refer
to
the
specificsection
of
the
manual
for
additional
requirements.
1.
All
field
wiring
must
be
installed
in
accordance
with
NFPA
70
National
Electric
Code,
CSA
C22.1
Canadian
Electrical
Code
Part
1,
CAN/ULC
‐
S524,
NBC,
NBC,
NFC,
AHJ,
and
local
code
requirements.
2.
Use
the
addressable
smoke
detectors
listed
in
the
compatibility
chart
(Appendix
‐
A:
Compatible
Devices).
3.
Use
UL/ULC
listed
notification
appliances
compatible
with
the
FW106S/FW106SC
from
those
specified
in
Appendix
‐
A:
Compatible
Devicesof
this
manual.
4.
A
full
system
verificationmust
be
performed
every
time
the
panel
is
programmed
or
reprogrammed.
Requirements
for
Local
Protected
Fire
Alarm
Systems
At
least
one
UL
listed
supervised
notification
appliances
must
be
used.