Installation
and
Operation
Manual
7
Specifications
and
Features
The
specifications
and
features
of
the
FW106S/FW106SC
Control
Panel
are
described
in
Table
2.
Table
2
FW106S/FW106SC
Control
Panel
Specifications
General
Digital
signal
processor
based
design,
fully
configurable
from
front
panel
with
password
protection
Environmental
Operating
temperature
:
32
‐
120
F
(0
‐
49
C)
Relative
humidity
:
Up
to
93%
@
90
F
(32
C)
To
be
installed
in
normal
dry
indoorenvironment
only
Primary
Supply
110
‐
120
VAC
60Hz
(3.86A),
or
220
‐
240
VAC
50Hz
(1.96A)
SecondaryPower
Supply
Two
12V
in
series
lead
‐
acid
batteries
set
Charging
capacity:
40AH
Power
Outputs
Internal
power
supply
for
AMI
ALUs
and
Addressable
Loop
Circuits
NOUs
and
Notification
Appliance
Circuits
XNUs,
External
Network
Circuits
ROUs
One
auxiliary
power
supply
Non
‐
Resettable/Resettable
Power
Output
(configurable)
Power
limited
24VDC
Output
current:
500mA
in
normal
standby,
1200mA
in
alarm
Power
Factor
Rating:
0.35
Special
application:
Compatible
devices
are
the
Annunciator
Model
FW121
/
FW121C
/FW122W
/
FW122R
/
FW122CW
/
FW122CR
and
IO
Module
Model
FW821.
CLASS
B
when
powering
annunciator
models
FW121
/
FW121C
/FW122W
/
FW122R
/
FW122CW
/
FW122CR
Relays
Output
One
programmable
relay
4
non
‐
programmable
status
relays
Status:
Alarm,
Supervisory,
Trouble,
Monitor
Form
C
Contact
Contact
Rating:
2A
30VDC
Power
Factor
Ration:0.35
Notification
Appliance
Circuits
Total
of
4
circuits
supported,
total
power
available
8A
2
Class
A
or
2
Class
B
circuits
on
each
NOU
Maximum
Current:
2A
per
NAC
circuit
Alarm
Voltage:
24V
nominal
Bell
code:
Temporal
3
Panel
supports
one
regulated
24
VDC
NAC,
or
four
specialapplication24VDC
NAC.
Refer
to
Table
20
for
specific
appliances/devices.
Max
line
loss:
1.8
V.