Ice Thickness Probe Diagnostics
148
Indigo NXT Ice Machine Troubleshooting Tips
If the initial numbers displayed
do not
change
or initial numbers
did not
increase by 3000
during scratch test:
•
Verify the ice thickness probe connector is
properly plugged into the board ( J11 ) and
the ice thickness probe wiring is correct . If
the wiring is incorrect, replace the ITP.
10. Unplug the ITP and set a VOM to DC voltage
scale – Measure voltage across Pin 1(+) Red
Wire and Pin 2(-) Black Wire:
−
Voltage Measures 3.25 to 3.35 VDC =
Replace the ITP.
−
Voltage does NOT measure 3.25 t0 3.35
VDC = Replace the Control Board.
Premature Harvest or Freeze Up
Содержание Welbilt Indigo NXT QuietQube
Страница 3: ... Welbilt Inc Welbilt Inc Engineered For Ease Overview INDIGO NXT 3 ...
Страница 17: ... Welbilt Inc Welbilt Inc Engineered For Ease QuietQube CVD Installation INDIGO NXT 17 ...
Страница 32: ... Welbilt Inc Welbilt Inc Engineered For Ease EasyTouch Installation Set Up Wizard INDIGO NXT Ice Machine 32 ...
Страница 50: ... Welbilt Inc Engineered For Ease Menu Navigation Indigo NXT Ice Machines ...
Страница 54: ... Welbilt Inc Indigo NXT Menu Navigation Alert 54 Touch Screen Interface Main Menu ...
Страница 55: ... Welbilt Inc Indigo NXT Menu Navigation Alert 55 Touch Screen Interface Main Menu ...
Страница 71: ... Welbilt Inc Welbilt Inc Engineered For Ease Sequence of Operation QuietQube CVD INDIGO NXT Ice Machines 71 ...
Страница 72: ... Welbilt Inc Remote IB CVD Ice machines 72 Indigo NXT QuietQube CVD Sequence of Operation Bin Probe ...
Страница 101: ... Welbilt Inc Welbilt Inc Engineered For Ease QuietQube Remote CVD Refrigeration System INDIGO NXT Ice Machine 101 ...
Страница 114: ... Welbilt Inc Welbilt Inc Engineered For Ease Troubleshooting INDIGO NXT Ice Machine 114 ...
Страница 125: ... Welbilt Inc Review 125 Symptom 1 Symptom 2 Symptom 3 Air Water Traditional Remote QuietQube Symptom 4 ...
Страница 126: ... Welbilt Inc Welbilt Inc Engineered For Ease Troubleshooting Tips INDIGO NXT Ice Machine 126 ...
Страница 153: ... Welbilt Inc Water Level Probe Diagnostics 153 Indigo NXT Ice Machine Troubleshooting Tips ...