Section 7
Refrigeration System
Part No. 80-1100-3
7-45
Q1600 SERIES
Remote
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
24 Hour Ice Production
Operating Pressures
Q1800 SERIES
Self-Contained Air-Cooled
NOTE: These characteristics may vary depending on
operating conditions.
Cycle Times
Freeze Time + Harvest Time = Total Cycle Time
24 Hour Ice Production
Operating Pressures
Air Temp.
Entering
Condenser
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
-20 to 70
-29 to 21.1
7.5-8.4
8.2-9.2
9.0-10.1
1 - 2.5
90/32.2
8.0-8.9
8.6-9.6
9.2-10.3
100/37.8
8.4-9.3
9.2-10.2
9.7-10.8
110/43.3
9.2-10.3
10.0-11.2
10.4-11.6
Times in minutes
Air Temp.
Entering
Condenser
°F/°C
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
-20 to 70
-29 to 21.1
1600
1478
1370
90/32.2
1523
1425
1340
100/37.8
1460
1350
1290
110/43.3
1343
1250
1213
Based on average ice slab weight of 13.0- 14.12lb
Ratings with JC1895 condenser, dice or half dice cubes
Air Temp.
Entering
Condenser
°F/°C
Freeze Cycle
Harvest Cycle
Discharg
e
Pressure
PSIG
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
-20 to 50/-29
to 10.0
220-255
52-26
100-120
70-85
70/21.1
250-270
56-28
110-120
75-90
80/26.7
250-275
56-28
110-120
75-90
90/32.2
255-285
56-28
110-120
80-90
100/37.8
270-310
56-30
115-130
80-95
110/43.3
305-350
58-32
120-135
80-100
Suction pressure drops gradually throughout the freeze cycle
Air Temp.
Entering
Condenser
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
70/21.1
8.5-9.3
9.4-10.3
9.9-10.9
1-2.5
80/26.7
9.0-9.9
9.8-10.8
10.5-11.5
90/32.2
9.6-10.5
10.4-11.5
11.1-12.2
100/37.8
10.6-11.6
11.5-12.6
12.4-13.6
Times in minutes
Air Temp.
Entering
Condenser
°F/°C
Water Temperature °F/°C
50/10.0
70/21.1
90/32.2
70/21.1
1880
1720
1640
80/26.7
1780
1650
1560
90/32.2
1690
1570
1480
100/37.8
1550
1440
1350
Based on average ice slab weight of 13.0 - 14.12lb
Regular cube derate is 7%
Air Temp.
Entering
Condenser
°F/°C
Freeze Cycle
Harvest Cycle
Discharg
e
Pressure
PSIG
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
50/10.0
220-280
40-20
155-190
60-80
70/21.1
220-280
40-20
160-190
65-80
80/26.7
230-290
42-20
160-190
65-80
90/32.2
260-320
44-22
185-205
70-90
100/37.8
300-360
46-24
210-225
75-100
110/43.3
320-400
48-26
215-240
80-100
Suction pressure drops gradually throughout the freeze cycle
Содержание QD0202A
Страница 3: ......
Страница 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Страница 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...