Section 7
Refrigeration System
Part No. 80-1100-3
7-15
Safety Limit #1
Refer to page 7-13 for control board identification and safety limit operation.
Control Board with Black Microprocessor -
Freeze Time exceeds 60 minutes for 3 consecutive freeze cycles
or
Control Board with Orange Label on Microprocessor -
Freeze time exceeds 60 minutes for 6 consecutive freeze
cycles
.
SAFETY LIMIT NOTES
•
Because there are many possible external problems,
do not limit your diagnosis to only the items listed in
this chart.
•
A continuous run of 100 harvests automatically
erases the safety limit code.
•
The control board will store and indicate only one
safety limit – the last one exceeded.
•
If the toggle switch is moved to the OFF position and
then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will
be indicated.
•
If the harvest light did not flash prior to the ice
machine restarting, then the ice machine did not stop
because it exceeded a safety limit.
Possible Cause
Check/Correct
Improper installation
See “Installation/Visual Inspection Checklist” on
Page 7-10
Water system
Low water pressure (20 psi min.)
High water pressure (80 psi max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water fill valve
Dirty/defective water dump valve
Defective water pump
Electrical system
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Restricted condenser
air flow (air-cooled models)
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air recirculation
Dirty condenser filter
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Restricted condenser water flow (water-cooled models)
Low water pressure (20 psi min.)
High water temperature (90°F/32.2°C max.)
Dirty condenser
Dirty/defective water regulating valve
Water regulating valve out of adjustment
Refrigeration system
Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control (remotes)
Defective harvest valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensables in refrigeration system
Plugged or restricted high side refrigerant lines or component
Содержание QD0202A
Страница 3: ......
Страница 14: ...General Information Section 1 1 4 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 34: ...Installation Instructions Section 2 2 20 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...Maintenance Section 3 3 16 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 93: ...Section 6 Electrical System Part No 80 1100 3 6 37 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 112: ...Electrical System Section 6 6 56 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 135: ...Section 7 Refrigeration System Part No 80 1100 3 7 23 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 168: ...Refrigeration System Section 7 7 56 Part No 80 1100 3 Figure 7 18 Using Pinch Off Tool SV1406 ...
Страница 174: ...Refrigeration System Section 7 7 62 Part No 80 1100 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 175: ...Section 7 Refrigeration System Part No 80 1100 3 7 63 THIS PAGE INTENTIONALLY LEFT BLANK ...