32
Installation, repairs and conversions may be done by qualified and authorised person only.
●
Visual check of the installation in regard of observation all applicable safety standards and regu-
lations.
●
Visual check of the appliance and accessories including the flue line.
●
Heating tubes and exhaust system permeability, their intactness and tightness.
●
Leakage test of gas connection from ball valve to burner incl. gas valve (foaming solution, gas
detector).
●
Inspection, eventually cleaning of the burner.
●
Inspection, eventually cleaning of the vacuum sensor.
●
Measuring the ventilation time of the appliance.
●
Exchange of the vacuum hose.
●
Manostat function check.
●
Inspection of ionisation and ignition electrodes, cleaning, and adjustment if necessary.
●
Performance check of the heater.
●
Measurement of jet pressures, eventually adjustment.
●
Flue gases measurement, eventually adjustment of parameters.
●
Safety elements of the appliance.
●
Solidity check of all electric connections.
●
Check of burner control functioning.
●
Check of signalization and switching functionality of control box.
●
Visual inspection of all electric insulations of the appliance, their exchange if needed.
- ventilator does
not work (no reaction to the release)
Defective ventilator
Replace the ventilator
Defective automatics
Replace the automatics
Faulty electric connection of the burner
box
Check the connection – exhaust box
Defective air manostat
Replace the air manostat
Defect in the burner box electric connec-
tion
Check the connection (cables)
No connection to the electric supply
Check the connection
Defective gas manostat
Replace the gas manostat
Low gas pressure in the distribution lines
Increase the pressure
-
Flue gas exhaustion clogged
Clean
Defective air manostat
Replace the air manostat
Defective manostat hose – break or
locked
Replace or clean
Defective automatics
Replace the automatics
Defect of the burner box electric installa-
tion
(cables)
Check the connection
- ventilator works only during the
aeration and starting (approx. 50s)
Defective electrodes or their setting
or defective electrode cables
Check, replace
Defective covering (orifice opening)
Check, set
Defective jet pressure setting
Set
Defective gas armature regulator
Replace the armature
Defective automatics
Replace
Low gas pipeline pressure
Increase the pressure