    During the installation process, the blade position must be “CLOSED”.

   During the installation process, the control mechanism must be protected against pollution and damage.

Fire  dampers  are  suitable  for  installation  in  any  position  in  vertical  and  horizontal  passages  of  fire
separating structures.

The gap between the installed damper and structure must be completely filled with approved material.

The distance between the fire damper and structure (wall, ceiling) must be at least 75 mm. If two or more
dampers are to be installed in one fire separating structure, the distance between the adjacent dampers
must be at least 200 mm.

   The damper blade (in its closed position) must be inside of the fire separating structure. The fire damper

may also be installed outside the wall structure. The piping and damper part between the wall structure
and damper blade (marked with the BUILT-IN EDGE label on the damper body) must be protected by
fire insulation.

Built-in edge

300

190

50

50

50

400

Содержание FDMR 60

Страница 1: ......

Страница 2: ...er EN 13501 3 A1 Fire damper FDMR Solid wall construction Mortar or gypsum Duct 100 40 Fire damper FDMR Solid wall construction Stuffing box mineral stone wool min density 140 kg m Fire protection mas...

Страница 3: ...tic min thickness 1 mm Fibreglass felt with aluminium foil thickness 5 mm width 50 mm Duct 100 Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with cor resp...

Страница 4: ...nsity 140 kg m Fire protection mastic min thickness 1 mm Fibreglass felt with aluminium foil thickness 5 mm width 50 mm Duct 40 Fire damper FDMR Solid ceiling construction Mortar or gypsum Duct 40 50...

Страница 5: ...5 300 50 120 D 110 400 180 50 300 50 53 110 400 180 50 D...

Страница 6: ...terial The distance between the fire damper and structure wall ceiling must be at least 75 mm If two or more dampers are to be installed in one fire separating structure the distance between the adjac...

Страница 7: ...rocess Once the damper is built installed its blade must not grind on the damper body during its opening or closing The damper installation procedures must completely exclude any transfer of loads fro...

Страница 8: ...al checks then operational checks may be completed once a year Prior to the commissioning of the dampers and subsequent operational checks the following checks must be completed with all the designs V...

Страница 9: ...status it is possible to remove the whole mechanism from the fire damper body the mechanism is attached to the damper body with four M6 screws After the thermal fuse removal from its holder in the ini...

Страница 10: ...stos free fire resistant mineral fibre boards The damper control devices are made of galvanized materials alternatively of stainless steel without any additional surface finish The springs are galvani...

Страница 11: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Отзывы: