Fire damper - FDMQ
Page 70
Version 2023-07-27
TPM 103/14
Installation frame E5
■
Installation frame E5 is designed for installation without additional sealing of the penetration for:
■
Installation in gypsum walls under flexible ceilings with a maximum movement of 40 mm
■
Wall thicknesses 100 to 150 mm
■
Installation frame is equipped with an intumescent sealing on the inside and outside. This sealing fills the gap between the
damper casing and frame and between the frame and construction in the event of a fire
■
Position of the damper can be directly on the ceiling or at a distance of max. 80 mm from the ceiling
■
Material:
■
Installation frame - cement-lime boards and galvanized steel
■
Fasteners - galvanized steel
Installation frame E5
50
110
B
+
2
2
4
B
+
1
0
4
A+104
A+208
(from promaseal)
A
B