19
TPM 083/12
1
2
3
5
4
Fig. 24
Suspension - horizontal duct
Position:
1
Fire damper
2
Damping pad
3
Extension piece
4
Threaded rod
5
Suspension ring
Examples of using materials:
HILTI, SIKLA, MÜPRO etc.
7.3.
Vertical installation
Fire dampers can be suspended by using threaded rods and a mounting profiles.
Load the suspension system depend on weight of the fire damper.
Damper can be suspended from the ceiling construction or supported above the ceiling construc-
tion. Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
2
5
4