Fig. 21
Gypsum wall construction - stuffing box and fire protection mastic
POSITION:
1
Fire damper FDMC
2
Gypsum plate
3
Fire resistant insulation
4
Mineral stone wool min. density 140 kg/m
5
Fire protection mastic min. thickness 1 mm
6
Glass fiber felt with aluminium foil width 50 mm, thickness 5 mm
7
Duct
Used materials - example*:
4 - Promapyr, Rockwool Steprock HD
5 - Promastop - P, K
Fig. 20
Gypsum wall construction - mortar or gypsum
4
5
≥
40
≥
100
2
3
POSITION:
1
Fire damper FDMC
2
Gypsum plate
3
Fire resistant insulation
4
Mortar or gypsum
5
Duct
1
* Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws
≥
3,5 mm
with corresponding length. Distance
between screws
≤
200 mm.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws
≥
3,5 mm
with corresponding length. Distance
between screws
≤
200 mm.
EIS 60
EIS 60
3