46
TPM 075/09
Fig. 58
Installation in solid ceiling construction
EIS 60
5
1
≥
150
≥
50
≥
50
3
4
≥
80
≥
50
3
4
≥
150
1
2
2
POSITION:
1
Fire damper FDMB
2
Stuffing box (mineral stone wool min. density 140 kg/m )
3
Fire protection mastic min. thickness 1 mm
Used materials - example*:
2 - Promapyr, Rockwool Steprock HD
3 - Promastop - P, K
* Stuffing box, fire protection mastic and insulation materials
can be replaced by another approved fire sealing system
for damper installation with equivalent material properties