7
TPM 075/09
Fig. 12 Actuating mechanism BELIMO BLF 24-T(-ST)
AC 24 V
~
1
2
+
-
DC 24 V
S2
S1
S3
S5
S4
S6
M
BLF24-T, BLF24-T-ST
an insulation transformer.
Parrallel connection of other driver is possible.
BLF24-ST-T: Design with connector plugs for communication
to network and communication device BKN230-24
Connection through
Pay attention to the power input data.
<5°
<80°
BAE72B-S
Tf1
Tf2
Tf3
LED
Fig. 13 Actuating mechanism BELIMO BLF 230-T
BLF230-T
M
AC230 V
2
1
N L1
S3
S2
S1
S6
S5
S4
For separation from the mains, a device that
insulates polar conductors must be at disposal
(Minimum distance between contacts - 3 mm).
<5°
<80°
BAE72B-S
Tf1
Tf2
Tf3
LED
Parrallel connection of other driver is possible.
Pay attention to the power input data.
Tab. 2.2.2. Actuating mechanism BELIMO BF 24-T(-ST), BF 230-T
Actuating mechanism BELIMO
BF 24-T(-ST)
BF 230-T
Nominal voltage
AC 24 V 50/60 Hz
DC 24 V
AC 230 V 50/60 Hz
Power consumption - motoring
- holding
7 W
2 W
8 W
3 W
Dimensioning
10 VA (Imax 8,3 A @ 5 ms)
12,5 VA (Imax 500 mA @ 5 ms)
Protection class
III
II
Degree of protection
IP 54
Running time - motor
- spring return
140 sec
~ 16 sec
Ambient Temperature
- normal duty
- safety duty
- non-operating temperature
- 20 °C … + 50 °C
The safe position will be attained up to max. 75°C
- 40 °C … + 50 °C
Connecting - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm
cable 1 m, 6 x 0,75 mm
(BF 24-T-ST) with plug-in connectors
Thermal trips
Tf1: duct outside temperature Duct 72 °C
Tf2/Tf3: duct intside temperature Duct 72 °C
2
2
Содержание FDMB