72
TPM 075/09
15.4.
Before entering the dampers with actuating mechanism into operation after their assembly and
by sequential checks, checks according 15.2. and following checks must be carried out.
Check of blade displacement into the breakdown position "CLOSED" can be done after cutting
off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical
starting mechanism BAE 72B-S or cutting off the supply from ELECTRICAL FIRE SIGNALISA-
TION). Check of blade displacement back into the "OPEN" position can be done after restoration
of power supply (e.g. By releasing the RESET button or restoration of supply from ELECTRICAL
FIRE SIGNALISATION).
16. Spare parts
16.1.
Spare parts are supplied only on basis of an order.
16.2.
Control for square damper and round damper is identical.
17. Restore function of actuating mechanism after fuses initiation
17.1.
If fuse Tf1 is initiated (duct outside temperature) than is necessary to change thermoelectrical
starting mechanism BAE72B-S. Whereas is initiation temperature higher than actuator
mechanism operating temperature +50°C, recommended actuating mechanism manufacturer
make complete revision or change actuating mechanism and thermoelectrical starting mechanism.
17.2.
If fuses Tf2/Tf3 are initiated (duct inside temperature) than is possible change only part ZBAE72,
or ZBAE95 (according initiating temperature).
VIII. PRODUCT DATA
18. Data label
18.1.
Data label is placed on the damper body.
Fig. 79 Data label
Certification:
WEIGHT (kg):
Dob
ř
íšská 550
267 24 Hostomice
MANDÍK, a.s.
Czech Republic
FIRE DAMPER FDMB-S
DESIGN:
SERIAL NUMBER:
SIZE:
1391
1391-CPD-0113/2012
12
EN 15650:2010
CLASSIFICATION:
EI 90 (ve ho i o) S
TPM075/09