BOXER SERIES 80-120 KVA
OPERATION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
41
4.1.3 Testing the Operation Modes of the UPS
After first start switch between operating modes for control of operation
4.1.3.1 Switching from Normal Mode to Battery Mode
Switch off CB1.This action cuts off the mains voltage and the UPS starts operating on battery
mode. After checking the operation, switch off CB1 again.