10. Replace battery fuse on battery cabinet.
11.If there is, switch the breakers on the battery cabinet to the position of “ON”.
12Check if there is appropriate battery voltages to the battery input terminals of the UPS by
means of a proper measuring device.
External battery cable selection is determined by application. Fuses which are recommended for
the UPS and battery cabinet are given. To connect to these type fuses, the lowest diameter cables
are suggested. Please, refer to the standard called EN 50525-2-31(VDE 0100-430) in this subject.
The selection should be such that the cable will allow at most 0.5 Vdc decreasing.
"
External Battery Temperature Measurement Kit
" provided for optimization of the batteries
according to battery temperatures in the external battery cabinet application. The batteries will
be optimized according to the temperature.