23
Majestic • JADE32IN, JADE42IN, JADE42IL Installation Manual • 2491-986 Rev. K
• 10/18
Top Vent - Horizontal Termination - (continued)
Two Elbows
Figure 4.11
Note
: Use SLP Series
components only.
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
V Minimum
H
1
+ H
2
Maximum
JADE42IN/JADE42IL
JADE32IN
90° Elbow
Not Allowed
1 ft.
305 mm
1 ft.
305 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft.
914 mm
4 ft.
1.2 m
6 ft.
1.8 m
4 ft.
1.2 m
6 ft.
1.8 m
15 ft.
4.6 m
5 ft.
1.5
15 ft.
4.6 m
H
1
+ H
2
MAX. =15 ft. (4.6 m)
V
1
+ H
1
+ H
2
MAX. = 40 ft. (12.2 m)
CAUTION: The SLP-HRC-SS termination caps are
not approved for use with these models. May lead to
elevated glass temperature that may cause tempered
glass breakage.
Note
: There MUST be a 25% reduction
in total H when using SLP-FLEX Series
(6-5/8 inch) vent except when using
the simple up and out installation. See
Figure 4.8.