Ventilation air from outdoors for unusually tight 
construction.
WARNING:  If the area in which the heater may be 
operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight 
construction, provide adequate combustion and 
ventilation air by one of the methods described in 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Section 5.3 or applicable local codes.
Unusually tight construction

 is defined as construc-

tion where:
a.  walls and ceilings exposed to the outside atmo-

sphere have a continuous water vapor retarder with 
a rating of one perm (6x10.

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed and

b.  weather stripping has been added on openable win-

dows and doors.

c.  caulking or sealants are applied to areas such as 

joints around window and door frames, between 
sole plates and floors, between wall-ceiling joints, 
between wall panels, at penetrations for plumbing, 
electrical and gas lines and at other openings.

If your home meets all of the three criteria above, you 
must provide additional fresh air.
You may provide two permanent openings:  one within 
12” of the ceiling and one within 12” of the floor.  Con-
nect these items directly to the outdoors or spaces 

open to the outdoors.  These spaces include attics 
and crawl spaces.  Follow the National Fuel Gas Code 
NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion 
and Ventilation for required size of ventilation grille or 
ducts.

IMPORTANT:

  Do not provide openings for inlet or 

outlet air into attic if attic has a thermostat-controlled 
power vent.  Heated air entering the attic will activate 
the power vent.
You may provide two permanent openings:  one within 
12” of the ceiling and one within 12” of the floor.  Con-
nect these items directly to the outdoors or spaces 
open to the outdoors.  These spaces include attics 
and crawl spaces.  Follow the National Fuel Gas Code 
NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion 
and Ventilation for required size of ventilation grille or 
ducts.

WARNING: The optional blower kit is equipped 
with a three prong (grounding) plug for your 
protection against shock hazard and should be 
plugged directly into a properly grounded three 
prong receptacle.

WARNING: Air openings that provide fresh air 
from an adjoining unconfined space shall not be 
blocked or obstructed in any way. Installation 
of unit should allow a minimum of 2” clearance 
from any part of the heater to any of the ventila-
tion openings.

VO370-2

Ventilation 

options 

3/26/99   djt

OPTION 1 - 

Vents to 

Adjoining 

Room

OPTION 2 

- Remove 

Door to 

Adjoining 

Room

OPTION 3 

- Vents to 

Adjoining 

Room

12”

12”

VO370-2

Fig. 2

  Ventilation options for confined spaces.

Содержание UV36RN

Страница 1: ...use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier call the re department Installa...

Страница 2: ...rts 19 Warranty 21 This book contains your operating and installation instructions and should be kept in a safe place For you to realize all the advantages and use of the reliable service that has bee...

Страница 3: ...r ammable material on or near the appliance This appliance must only be used with pressures at the inlet as shown in Table 1 Page 11 in installation instructions The installation must conform with loc...

Страница 4: ...epth 7436 UV36RN rp Specs 11 4 03 djt 35 33 1 2 3 7 8 11 8 Outside Air Access Gas Line Access Not used on this model Gas Line Access 3 7 8 8 Gas Line Electrical Access Gas Line Access Not used on this...

Страница 5: ...pliances in the space Gas range_________________ BTU Hr Vented gas heater __________ BTU Hr Gas replace logs___________ BTU Hr Other gas appliances _____ BTU Hr Total _____ BTU Hr Example Gas range 60...

Страница 6: ...oors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size...

Страница 7: ...full outer casing and full bottom pan use Blower Kit BL 4 or FK12 If the construction of your replace is with two sheet metal legs supporting the combustion chamber at the back use Blower Kit BL 3 Th...

Страница 8: ...st boards etc is 9 Combustible material projecting 6 a mantel shelf for example requires a minimum clearance of 12 above the replace opening Required clearance varies with the amount of projection Fig...

Страница 9: ...F THE CANOPY UNDER THE LOOSENED SCREWS THEN RETIGHTEN THE SCREWS TO SECURE THE CANOPY Fig 5a Step 2 Install the Firebox Install the rebox into the framed opening by setting it directly in front of the...

Страница 10: ...ater s rating plate If the gas type indicated on the plate is not your type of gas supply DO NOT INSTALL Contact your dealer for proper model Gas Piping The gas supply line must be of an ad equate siz...

Страница 11: ...determine the size of the branch gas line from the main gas line to the replace enter the tables below for iron pipe or copper tubing using the distance from the gas meter or second stage regulator t...

Страница 12: ...nly on top of the front burner port area Equally space embers one layer thick Do not pile ember material over one layer thick as this does not enhance the ember appearance or improve the log set perfo...

Страница 13: ...B B A T148 attach wires 11 5 03 djt A Existing valve wiring Do not tamper with B Remote receiver wires red or white on either side Fig 12 Attach receiver wires to outer two terminals on valve Installa...

Страница 14: ...tructions 1 STOP Read the safety information above before proceed ing 2 Refer to Figure 16 To turn off the gas supply depress the knob slightly and turn clockwise to the OFF position 3 Wait ve 5 minut...

Страница 15: ...hutter Settings Model A UV36RN 0 125 UV36RP 0 375 T134 Fig 23 Air shutter settings Finishing the Fireplace There are a wide variety of nishing materials avail able for your replace from formal wall tr...

Страница 16: ...d combination of ame aesthetics and heat output Fig 24 Finishing options T146 finishing 11 5 03 djt Wallboard with Marble Slate or Tile Facing Brick or Stone Facing Wallboard with Facing and Mantel Fi...

Страница 17: ...acuum cleaner to carefully remove dust and loose par ticles from the base logs and from around the burner Gloves are recommended when handling the logs Use extreme caution when cleaning around the pil...

Страница 18: ...clogged Clean burner ori ce Control knob not in ON position Turn control knob to ON position 4 Heater shuts off on ODS Not enough fresh air is available Open window Low gas pressure Contact your gas s...

Страница 19: ...s at any time without notice 7436 UV36RN UV36RP Ref Description UV36RN UV36RP 1 Grate Assembly 78442 78442 2 Side De ector 78443 78443 3 Support Channel 78439 78439 4 Air Scoop 78445 78445 5a Valve Na...

Страница 20: ...78596 78596 14 Mini Rocker Switch PCOA049 PCOA049 15 Knob Extension On Off 3 77958 77958 16 Knob Extension Hi Lo 3 77959 77959 17 Embers Platinum Bag 78037 78037 18 Lava Gravel Assy 68688 68688 19 Log...

Страница 21: ...21 UV36RN RP Vent Free Gas Fireplaces 20007436...

Страница 22: ...22 UV36RN RP Vent Free Gas Fireplaces 20007436...

Страница 23: ...ction the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: