UV36RN/RP Vent-Free Gas Fireplaces

20007436

When installing this fireplace at an elevation above 
2,000 feet, it may be necessary to decrease the input 
rating by changing the existing burner orifice to a small-
er size.  Input should be reduced four percent (4%) for 
each 1,000 feet above sea level, unless the heating 
value of the gas has been reduced, in which case this 
general rule will not apply.  To identify the proper orifice 
size, check with the local gas utility.
Consult your local gas utility for assistance in determin-
ing the proper orifice for your location.

Gas Pressure Check

The gas inlet pressure specified in Table 1 is the pres-
sure where the field-installed gas line connects to the 
gas control. This is measured at the inlet test port on 
the gas valve in the appliance. Ensure that pressure is 
as shown in Table 1.
The manifold pressure is controlled by a regulator built 
into the gas control and should be checked at the pres-
sure test points located between the flame adjustment 
knob and the control knob at the front of the valve. The 

 

Table 1

 

 

Gas Inlet Pressure  

Natural  

Propane

 

Max. 

14.0” w.c. 

14.0” w.c.

 

Normal 

7.0” w.c. 

11.0” w.c.

 

Min.* 

4.5” w.c. 

11.0” w.c.

 

Regulator Pressure

 

3.5” w.c. 

10.0” w.c.

*Minimum inlet supply pressure for the purpose of input adjustment.

pressure connections accept 1/4” I.D. hose or tubing.
The pressure should be checked with the appliance 
burning on high (highest setting) and all other gas ap-
pliances turned on. One must then read the manometer 
and if pressures are not as specified in Table 1, then 
the inlet pressure must be adjusted.
After measuring the pressure, tighten the screw in the 
pressure test port and check for leaks. Replace the 
control box cover and the two screws.

NOTE:  To determine the size of the branch gas line from the main gas line to the fireplace, enter the tables below (for 
iron pipe or copper tubing) using the distance from the gas meter or second stage regulator to the furthest appliance on 
the gas system.  Select a pipe or tube diameter which has enough capacity to meet the maximum input requirement of 
the fireplace.  Regardless, do not use less than 1/2” diameter for the branch line.  For any distances required longer than 
shown in these tables, refer to the National Fuel Gas Code.

NOTE:  There may be a local gas utility requirement specifying a minimum diameter for gas piping.  All units require a 1/2 inch pipe con-
nection at the gas valve.

Gas Line Pipe Sizing

CAPACITY OF PIPING

Cubic Feet per Hour based on 0.3” w.c. Pressure Drop

Specific Gravity for Natural Gas - 0.6 (1000 BTU/Cubic Foot)

Specific Gravity for Propane Gas - 1.6 (2550 BTU/Cubic Foot)

 

Length 

Nominal Inches for Iron Pipe Sizes (1,000s BTU/hr)

 

of 

1/2” D 

3/4” D 

1” D 

1

¹⁄₄

” D 

1

¹⁄₂

” D

 

Pipe 

Natural  Propane  Natural  Propane  Natural  Propane  Natural 

Propane  Natural  Propane

 

20’ 

92 

143 

190 

296 

350 

546 

730 

1135 

1100 

1711

 

30’ 

73 

115 

152 

237 

285 

444 

590 

918 

890 

1385

 

40’ 

63 

97 

130 

202 

245 

380 

500 

778 

760 

1183

 

50’ 

56 

87 

115 

179 

215 

334 

440 

683 

670 

1043

 

60’ 

50 

79 

105 

163 

196 

304 

400 

622 

610 

949

 

70’ 

46 

71 

96 

151 

180 

280 

370 

576 

560 

872

 

90’ 

40 

61 

84 

130 

160 

250 

320 

497 

490 

763

 

100’ 

38 

59 

79 

122 

150 

235 

305 

474 

460 

717

 

Outside Diameter Copper Tubing, Type L (1,000s BTU/hr)

 

Tubing Length 

1/2” 

5/8” 

3/4” 

7/8”

 

Feet 

0.43 

0.545 

0.666 

0.785

 

10 

110 

206 

348 

536

 

20 

76 

141 

239 

368

 

30 

61 

114 

192 

296

 

40 

52 

97 

164 

256

 

50 

46 

86 

146 

224

 

60 

42 

78 

132 

203

 

80 

36 

67 

113 

174

 

100 

32 

59 

100 

154

WARNING: Use only internally tinned copper tubing. If correct copper tubing is not used, tubing can deteriorate and  de-
velop gas leaks.

CAUTION: If the appliance’s operating pressures 
are not checked and adjusted, improper combus-
tion may result in soot being produced.

Содержание UV36RN

Страница 1: ...use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier call the re department Installa...

Страница 2: ...rts 19 Warranty 21 This book contains your operating and installation instructions and should be kept in a safe place For you to realize all the advantages and use of the reliable service that has bee...

Страница 3: ...r ammable material on or near the appliance This appliance must only be used with pressures at the inlet as shown in Table 1 Page 11 in installation instructions The installation must conform with loc...

Страница 4: ...epth 7436 UV36RN rp Specs 11 4 03 djt 35 33 1 2 3 7 8 11 8 Outside Air Access Gas Line Access Not used on this model Gas Line Access 3 7 8 8 Gas Line Electrical Access Gas Line Access Not used on this...

Страница 5: ...pliances in the space Gas range_________________ BTU Hr Vented gas heater __________ BTU Hr Gas replace logs___________ BTU Hr Other gas appliances _____ BTU Hr Total _____ BTU Hr Example Gas range 60...

Страница 6: ...oors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size...

Страница 7: ...full outer casing and full bottom pan use Blower Kit BL 4 or FK12 If the construction of your replace is with two sheet metal legs supporting the combustion chamber at the back use Blower Kit BL 3 Th...

Страница 8: ...st boards etc is 9 Combustible material projecting 6 a mantel shelf for example requires a minimum clearance of 12 above the replace opening Required clearance varies with the amount of projection Fig...

Страница 9: ...F THE CANOPY UNDER THE LOOSENED SCREWS THEN RETIGHTEN THE SCREWS TO SECURE THE CANOPY Fig 5a Step 2 Install the Firebox Install the rebox into the framed opening by setting it directly in front of the...

Страница 10: ...ater s rating plate If the gas type indicated on the plate is not your type of gas supply DO NOT INSTALL Contact your dealer for proper model Gas Piping The gas supply line must be of an ad equate siz...

Страница 11: ...determine the size of the branch gas line from the main gas line to the replace enter the tables below for iron pipe or copper tubing using the distance from the gas meter or second stage regulator t...

Страница 12: ...nly on top of the front burner port area Equally space embers one layer thick Do not pile ember material over one layer thick as this does not enhance the ember appearance or improve the log set perfo...

Страница 13: ...B B A T148 attach wires 11 5 03 djt A Existing valve wiring Do not tamper with B Remote receiver wires red or white on either side Fig 12 Attach receiver wires to outer two terminals on valve Installa...

Страница 14: ...tructions 1 STOP Read the safety information above before proceed ing 2 Refer to Figure 16 To turn off the gas supply depress the knob slightly and turn clockwise to the OFF position 3 Wait ve 5 minut...

Страница 15: ...hutter Settings Model A UV36RN 0 125 UV36RP 0 375 T134 Fig 23 Air shutter settings Finishing the Fireplace There are a wide variety of nishing materials avail able for your replace from formal wall tr...

Страница 16: ...d combination of ame aesthetics and heat output Fig 24 Finishing options T146 finishing 11 5 03 djt Wallboard with Marble Slate or Tile Facing Brick or Stone Facing Wallboard with Facing and Mantel Fi...

Страница 17: ...acuum cleaner to carefully remove dust and loose par ticles from the base logs and from around the burner Gloves are recommended when handling the logs Use extreme caution when cleaning around the pil...

Страница 18: ...clogged Clean burner ori ce Control knob not in ON position Turn control knob to ON position 4 Heater shuts off on ODS Not enough fresh air is available Open window Low gas pressure Contact your gas s...

Страница 19: ...s at any time without notice 7436 UV36RN UV36RP Ref Description UV36RN UV36RP 1 Grate Assembly 78442 78442 2 Side De ector 78443 78443 3 Support Channel 78439 78439 4 Air Scoop 78445 78445 5a Valve Na...

Страница 20: ...78596 78596 14 Mini Rocker Switch PCOA049 PCOA049 15 Knob Extension On Off 3 77958 77958 16 Knob Extension Hi Lo 3 77959 77959 17 Embers Platinum Bag 78037 78037 18 Lava Gravel Assy 68688 68688 19 Log...

Страница 21: ...21 UV36RN RP Vent Free Gas Fireplaces 20007436...

Страница 22: ...22 UV36RN RP Vent Free Gas Fireplaces 20007436...

Страница 23: ...ction the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: