8. Troubleshooting . CBA UP
8.1 Failure causes and solutions
Faulty group drives
Group drive command responds only the single device
Please check if the toggle switch master is activated on the desired device.
Not all blind actuators respond during a group drive
It could be possible that there are several masters defined in the group.
Please make sure that only the master is configured with a fixture "... Group".
Timer does not completely finish with animations
Please check if the drive time of the devices is longer than the set Drive time of the animation.
8.2 Unpair devices from network
Unpair a device from an existing network
A device that is integrated into a Casambi network can be removed from the network again with the function "unpair device".
Ein Gerät, dass in ein Casambi Netzwerk eingebunden ist, kann über die Funktion Gerät entkoppeln wieder aus dem Netzwerk entfernt
werden.
Devices nearby
Select device
Unpair device
A successful unpairing is indicated in the app.
By unpairing from a network, the parameters and settings of the device are removed.
Unpair device from a network to which you no longer have access
To unpair a device to which you have physical access to from a network, you can use the function flick-unpairing.
To do this, the function "Allow flick-unpairing" must be activated.