14 RLS 45 K – commissioning software | UK
63
Parameter
Set value
PPB 30 K button
start delay
0 ... 120 sec.
PPB 30 K duration
button function
5 ...
10
... 90 min.
No. of
power units
No
other PUs/RLS’
1 PU/RLS
2 PUs/RLS’
3 PUs/RLS’
Slave no. 1
Slave no. 2
Slave no. 3
RLS 45 K function
230 VAC input
Sleep function
intermittent ventilation
safety function
supply air function
Function
supply air function
overrun time
No overrun time
6 min. overrun time
15 min. overrun time
Modbus
communication
deactivated
activated
Modbus
baud rate
9600 baud
,
19200 baud
Modbus
address
10
... 50
Restore factory
settings
Keep settings
restore factory
settings
i
When using the RS-485 interface
as the Modbus interface,
no
other components (sensors,
power units, room air controls
etc.) can be connected to this
interface.
Ventilation
Parameter
Set value
Filter service life
unit filter
1 ...
6
... 8 months
Filter change
unit filter:
Acknowledgement
changed,
not changed
Duration ventilation
level level 5 (intermit-
tent ventilation)
5 ...
30
... 90 minutes
Duration night time
level 0 (sleep mode):
15 ...
60
... 120 mi-
nutes
Ventilation level
Off*
Off blocked
Off possible
* Select
Ventilation level 0 “Off blocked”,
if you want to ensure continuous ventilation
operation. The ventilation units can then no
longer be switched off.