14 RLS 45 K – commissioning software | UK
65
i
Before selection of “5. PP 45 RC lear-
ning mode”, it is necessary to define
the PP45 RC devices amongst them
selves as master/slave.
i
PP45 RC devices only function in pairs
and only wish master/slave assignment.
Parameter
Set value
Deactivate learning-in
Manual EEP input
Following table
Change name
bathroom, living room
etc.
Unlearn units
All released EnOcean
components are un-
learned
Radio components which can be learned-in
You can learn-in up to 8 connected EnOcean
components. PP 45 radio components must
support the EEP protocol. Radio components
with the same EEP no. can be combined with
the PP 45 system.
Radio components which can
be learned-in
EEP
EasySens radio switch,
4-channel wall transmitter
F6-02-01
Humidity/temperature sensor
A5-04-01
CO
2
/temperature sensor
A5-09-08
VOC/temperature sensor*
A5-09-05
ViAct (Opus Bridge) 1-channel
recessed-mounted switch
D2-01-01
* no EnOcean VOC sensor currently available.
Complete commissioning/maintenance
To save a commissioning or maintenance
protocol. This includes project data, infor
-
mation regarding the planner, installer and
customers as well as notes.
The unit date, all settings and a fault logbook
are automatically stored.
A print file is generated so that you can save
or print it.
Input/read out data set
To read out or input the device configurations.
This can, for example, be sent to the manu
-
facture in case servicing is needed. Externally
created configuration data can be input.