21
CONTROLLER ALARM LIST WITH DESCRIPTION
Alarm Display
Shutdown
or Alarm
Description
Possible Cause
Wrn Oil press
Alarm
Warning level of oil pressure reached
Low oil, faulty sender, low engine oil pressure
Sd Oil press
Shut Down
Shutdown Level of oil pressure reached
Low oil, faulty sender, failed engine
Fls Oil Pressure
Alarm
False Oil Pressure Sender Signal
Sending unit / wiring defective
Wrn Wtemp Low
Alarm
Warning water temp is cold
Cold exterior, block heater not functioning
Wrn Water temp
Alarm
Warning for High water temp
Low water level, thermostat, faulty sending unit,
poor radiator performance
Sd Water temp
Shut Down
Shutdown level for high water temp
Low water level, thermostat, faulty sending unit,
poor radiator performance
Fls Water Temp
Alarm
False Water Temp Sender Signal
Sending unit / wiring defective, water temp
outside of sender curve
Wrn Fuel Level
Alarm
Warning level for Low Fuel
Low fuel / faulty sender
Sd Fuel Level
Shut Down
Shutdown for Low Fuel Level
Low fuel, faulty sender
FLS Fuel Level
Alarm
False Fuel Level Signal
Sending unit / wiring defective
Emergency Stop
Shut Down
E stop mechanism has been activated
Emergency Stop has been activated
Wrn Overload
Alarm
Warning level of kW overload reached
Approaching kW overload shutdown
Sd Overload
Shut Down
Shut down level of kW overload reached kW draw on generator is to high
Sd Underspeed
Shut Down
Shutdown level for underspeed Reached Fuel, air, generator load
Stop Fail
Shut Down
Controller expects unit to be shutdown,
but is receiving engine running data
Fuel rack stuck
Sd Overspeed
Shut Down
Shutdown level for Overspeed reached
Slow reaction to rapid unload, Engine governor,
incorrect flywheel setting
Wrn Batt Volt
Alarm
Warning level for high or low battery
voltage
Replace alternator, DC voltage regulator, battery
Wrn Vg1 Under
Alarm
Warning level for Line 1 under voltage
No generator output, Voltage regulator, safety
switch
Wrn Vg2 Under
Alarm
Warning level for Line 2 under voltage
No generator output, Voltage regulator, safety
switch
Wrn Vg3 Under
Alarm
Warning level for Line 3 under voltage
No generator output, Voltage regulator, safety
switch
Sd Vg1 Under
Shut down
Shutdown level for Line 1 under voltage
No generator output, Voltage regulator, safety
switch
Sd Vg2 Under
Shut Down
Shutdown level for Line 1 under voltage
No generator output, Voltage regulator, Safety
switch
Sd Vg3 Under
Shut Down
Shutdown level for Line 1 under voltage
No generator output, Voltage regulator, safety
switch
Wrn Vg1 Over
Alarm
Warning level for Line 1 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Wrn Vg2 Over
Alarm
Warning level for Line 2 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Wrn Vg3 Over
Alarm
Warning level for Line 3 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Sd Vg1 Over
Shut Down
Shutdown level for line 1 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Sd Vg2 Over
Shut Down
Shutdown level for line 2 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Sd Vg3 Over
Shut Down
Shutdown level for line 3 over voltage
Voltage regulator, voltage adjustment after V-
detect time delay
Sd Igen Unbal
Shut Down
Shutdown level for Generator current
unbalance condition
Generator load is unbalanced, failed equipment
Sd Vgen Unbal
Shut Down
Shutdown level for generator voltage
unbalanced
Generator load is unbalanced, failed equipment
Wrn Fgen Under
Alarm
Warning for generator under frequency
Fuel, air, generator load
Sd Fgen Under
Shut Down
Shutdown for generator under frequency Fuel, air, generator load
Wrn Fgen Over
Alarm
Warning level for Generator over
frequency
Slow reaction to rapid unload, Engine governor,
incorrect flywheel setting
Sd Fgen Over
Shut Down
Shut down level for Generator over
frequency
Slow reaction to rapid unload, Engine governor,
incorrect flywheel setting
Sd IDMT
Shut Down
Shut down for delayed overcurrent
Generator current is higher than setpoint, reduce
load
Sd Short Igen
Shut Down
Shut down for instantaneous current
overload
Generator is overloaded, possible motor starting
issue, reduce load
Wrn Service Time
Alarm
Time to service has expired
Engine needs service, reset time to service
interval clock
Содержание MLG 25
Страница 1: ...25 www m p llc com DIESEL GENERATOR MLG 25 OPERATION PARTS MANUAL...
Страница 28: ...28 ENCLOSURE ASSEMBLY 4 3 5 6 1 9 8 11 14 7 16 15 10 13 12 24 22 21 19 20 18 17 9 10 5 6 3 25 26 23 21 2 27...
Страница 30: ...30 AUXILIARY OUTLET PANEL ASSEMBLY 1 2 8 9 5 4 3 6 7 10 11 13 12 14 15 17 16 18...
Страница 34: ...ENGINE COOLING ASSEMBLY 34 1 2 3 7 3 12 6 22 4 5 2 1 13 14 15 16 17 8 19 20 9 6 11 18 10 21 6...
Страница 48: ...48 ALT EXIT ALT EXIT FUEL FUEL PUMP PUMP MLG 25 DC WIRING DC WIRING SCHEMATIC FOR UNITS BUILT PRIOR TO MAY 2006...