AUXILIARY OUTLETS
The control panel is equipped with six outlets for
running accessories or tools from the generator.
Power is supplied to the outlets any time the en-
gine is running and the main circuit breaker and
the auxiliary outlet main circuit breaker are switched
on “I”.
Should the main breaker trip, or the auxiliary out-
let main circuit breaker trip, remove some of the
load to the outlets before turning them back on.
Note: To ensure proper grounding, anytime the
generator is providing power to any equipment or
load panels that do not have a grounded plug a
ground wire must be added between the equipment and the grounding stud on the outlet panel per any
local, state or NEC codes and guidelines.
VOLTAGE REGULATION
System stability is the ability of the generator to respond to load transients. Decreasing stability makes the
generator less sluggish and faster to respond to load transients. If the stability of the regulator is de-
creased too much, the generator will tend to hunt under steady state conditions. To adjust the regulation,
see the included manual for the voltage regulator. The regulator is located behind the control panel on the
back of the generator box.
FINE VOLTAGE ADJUSTMENT
The output voltage can be fine adjusted after the generator is running by using the fine voltage adjustment
knob. The switch is located directly below the control power switch next to the control panel. This rheostat
will provide an increase (“+”) or a decrease (”-”) in the output voltage. To adjust the voltage, check the
output voltage on the LCD display. Turn the knob in the desired direction until the required voltage is shown
on the LCD display.
EMERGENCY STOP SWITCH
The generator is equipped with one emergency stop switch,
located on the side panel next to the auxiliary outlet panel.
The switch is clearly labeled with “
EMERGENCY STOP
” and
is red in color. The switch can be accessed and activated
with all doors closed and locked.
Activate the emergency stop switch by pushing the red but-
ton in until it locks down. This will trip the main circuit breaker
which will open the contact disconnecting the load to the con-
nection lugs. This will also open the fuel pump solenoid, shut-
ting down the engine and the Emergency Stop fault will be
displayed on the LCD. The switch will remain closed until it is
pulled out.
CAUTION! Use the EMERGENCY STOP only when the generator must be shut down immediately.
For any other shut down, follow the detailed shut down procedure.
15
AUXILIARY OUTLET
GROUNDING STUD
Содержание MLG 25
Страница 1: ...25 www m p llc com DIESEL GENERATOR MLG 25 OPERATION PARTS MANUAL...
Страница 28: ...28 ENCLOSURE ASSEMBLY 4 3 5 6 1 9 8 11 14 7 16 15 10 13 12 24 22 21 19 20 18 17 9 10 5 6 3 25 26 23 21 2 27...
Страница 30: ...30 AUXILIARY OUTLET PANEL ASSEMBLY 1 2 8 9 5 4 3 6 7 10 11 13 12 14 15 17 16 18...
Страница 34: ...ENGINE COOLING ASSEMBLY 34 1 2 3 7 3 12 6 22 4 5 2 1 13 14 15 16 17 8 19 20 9 6 11 18 10 21 6...
Страница 48: ...48 ALT EXIT ALT EXIT FUEL FUEL PUMP PUMP MLG 25 DC WIRING DC WIRING SCHEMATIC FOR UNITS BUILT PRIOR TO MAY 2006...