background image

Page 46

© 

2017 Sensata Technologies

Using AC Coupling

5.0  Using the MS-PAE Series in an AC Coupled Application

This section covers the use of MS-PAE Series inverter/chargers in an AC coupled system.

5.1 

What is an AC Coupled System

Many homeowners utilize renewable energy (e.g., PV, wind, etc.) by installing high ef

fi

 ciency, 

battery-less, grid-tie inverter systems to offset their power consumption from the utility grid. 

However, during a utility power outage, the grid-tie inverter normally stops operating. This can 

cause considerable frustration as the homeowner realizes that the critical loads in the home (e.g., 

refrigerator, lights, water pump, etc.) are no longer powered, and all the energy produced by the 

renewable energy source is being wasted while the utility power is out.
In an AC coupled system, since all the energy sources and loads are connected directly to the 

AC side, an option would be to install a bi-directional battery-based inverter, such as the MS-PAE 

Series. The MS-PAE Series would allow the existing battery-less, grid-tie inverter to continue 

operating during a power outage; thereby, continuing to utilize the renewable energy to power 

the home’s critical loads—all from the AC side. However, in an AC coupled system—during a utility 

power outage—the utility grid is not available to export any excess power that is generated. This 

means there may be more power produced than the critical loads can consume, causing this 

excess current to be pushed back through the output of the inverter into the battery bank. Since 

this is not the normal path for the inverter to control incoming current, it is unable to regulate the 

battery voltage, providing the possibility that the battery voltage will rise and cause damage to 

your batteries. However, the MS-PAE Series inverter includes a “frequency shift” feature that can 

be used to regulate the battery voltage by changing its output frequency.

5.2 

Frequency Shift Feature

The frequency shift feature—when enabled—causes the output frequency of the MS-PAE Series 

inverter (

Version 6.0) to change based on the inverter’s battery voltage. If the battery voltage 

begins rising, the output frequency starts decreasing; as the battery voltage returns to its correct 

voltage level, the frequency increases.
In an AC coupled system, the MS-PAE Series inverter is optimized to work with Magnum Energy’s 

MicroGT500

1

 grid-tie inverter to regulate the battery voltage. During a utility power interruption, if 

the battery voltage begins to rise above the custom-absorb voltage level, the output frequency of 

the MS-PAE Series will start shifting down. The MicroGT500 grid-tie inverter responds by decreasing 

its output current to avoid overcharging the battery. As the battery voltage falls, the MS-PAE Series 

frequency starts shifting back up allowing the MicroGT500 inverter to gradually provide more 

current so that the battery can return to its custom-absorb voltage level. The response time and 

whether the frequency continues to shift down or start shifting back up depends on how fast the 

battery voltage rises or returns to the custom-absorb voltage level. 

Note

1

: If you are using a grid-tie inverter other than the MicroGT500, you may need to use an additional 

primary battery management system to ensure the batteries are not overcharged. This may require 

you to install a diversion controller and a load capable of absorbing the majority of the expected surplus 

energy. Options include: 1) a DC diversion controller and DC resistance loads; 2) AC diversion using AC 

resistance loads driven by DC controlled relays; or, 3) Sensata’s AC Load Diversion controller (ACLD-40).

5.3 Con

fi

 guring a Remote to work in an AC Coupled System

A remote control (ME-RTR, ME-ARC, or ME-RC) is required and must be con

fi

 gured in order for 

the MS-PAE inverter to work optimally in an AC coupled system—as described below:
1.  Enable Frequency Shift: Under the SETUP button, set the 

Battery Type

 menu setting to “Custom”.

2.  Turn off Search mode: Adjust the SETUP button’s 

Search Watts

 menu setting to “OFF”.

3.  Turn off Parallel Threshold (ME-RTR only): Adjust the SETUP button’s 

Inverter Threshold

 

to 

Start Parallel

 menu setting to “OFF”.

4.  Ensure the MS-PAE is set to automatically accept grid power when available (ME-ARC and ME-

RTR only): Adjust the CTRL button’s 

AC In Control

 menu setting to “Auto Connect”.

Содержание Sensata MagnaSine

Страница 1: ...MS PAE Series Pure Sine Wave Inverter Charger Owner s Manual...

Страница 2: ...or system If the MS PAE inverter fails it is reasonable to assume the health of the user or other persons may be endangered Copyright Notice Copyright 2017 by Sensata Technologies All rights reserved...

Страница 3: ...sconnected from all sources Use Class 1 wiring methods for field wiring connections to terminals of a Class 2 circuit Listed or labeled equipment shall be installed and used in accordance with any ins...

Страница 4: ...ur voice or close enough to come to your aid when working around batteries Use proper lifting techniques when working with batteries Never use old or untested batteries Check each battery s label for...

Страница 5: ...x bornes d un circuit de Classe 2 Cot ou tiquet s quipement doit tre install et utilis conform ment aux instructions figurant dans la liste ou l tiquetage Toujours v rifier le c blage avant de commenc...

Страница 6: ...gamme de votre voix ou suffisamment pr s pour vous venir en aide lorsque vous travaillez pr s des batteries Utiliser des techniques de levage appropri es lorsque vous travaillez avec des piles Ne jam...

Страница 7: ...Sensor Installation and Wiring 16 2 2 6 Wiring the Inverter to the Battery Bank 17 2 3 AC Wiring 18 2 3 1 Pre AC Wiring Requirements 18 2 3 2 AC Wire Size and Overcurrent Protection 18 2 3 3 Recommen...

Страница 8: ...he MS PAE Series in an AC Coupled Application 46 5 1 What is an AC Coupled System 46 5 2 Frequency Shift Feature 46 5 3 Configuring a Remote to work in an AC Coupled System 46 6 0 Troubleshooting 47 6...

Страница 9: ...10 Connecting the MS PAE to Three Phase Power using a Buck Boost Transformer 23 Figure 2 11 Connecting the MS PAE Directly to Three Phase Power 23 Figure 2 12 Grounding System for MS PAE Series 24 Fig...

Страница 10: ...x D for clarification The MS PAE Series inverter charger includes the following 4000 watt model in a small footprint less area needed for installation Ability to parallel up to four identical MS PAE i...

Страница 11: ...ppliances to be run from the storage battery bank When the battery bank becomes discharged either renewable DC sources solar wind or hydropower can be used to recharge the batteries or a generator can...

Страница 12: ...connect this parallel Stack port to a ME RTR router Although the cabling and connectors used in this network system are the same as ethernet connectors this network is not an ethernet system Attempti...

Страница 13: ...odate and hold the AC input and output field wiring 9 Intake Air Vents ventilation openings that pull in air to keep the inverter cool for peak performance 10 Positive DC Terminal a 360 degree connect...

Страница 14: ...ng connections Remove the two screws to access the AC wiring terminal block 16 Input Circuit Breakers CB1 and CB2 these circuit breakers protect the unit s internal wiring and pass thru relay on each...

Страница 15: ...in a parallel configuration follow the information in this section and refer also to Section 4 0 for specific parallel instructions 2 1 Pre Installation 2 1 1 Unpacking and Inspection Carefully remov...

Страница 16: ...ut Utility Power 120 240VAC Output ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF BTS ME SBC Smart Battery Combiner Magnum Accessory ME AGS N Auto Gen Start...

Страница 17: ...te ventilation If the inverter is installed in an enclosure a fresh air intake opening must be provided directly to the front side intake vents of the inverter and an exhaust opening on the back side...

Страница 18: ...to the inverter Info Sensata provides a back plate with a suitable surface for mounting the inverter These back plates also provide the ability to mount either the MMP Series enclosure PN BP MMP or th...

Страница 19: ...2 5 1 cm 4 12 4 cm 4 12 4 cm 13 34 9 cm 12 32 1 cm 12 30 5 cm 6 16 8 cm 8 20 3 cm Exhaust Air Vents Exhaust Air Vents Air Intake Vents Air Intake Vents Top 30 30 30 Mounting Holes Keyhole slots x4 Mou...

Страница 20: ...one by feeding the wires through conduit Sensata provides a conduit box ME CB or MPX CB a single inverter enclosure MMP Series and a multiple inverter enclosure MP Series that include knockouts to con...

Страница 21: ...ative connection of each device is always connected before connecting disconnecting any battery positive CAUTION Before wiring the DC cables review the safety information at the beginning of this manu...

Страница 22: ...uipment Ground Wire BTS BTS Battery Bank Battery Bank s Equipment Ground Wire Battery Bank s Negative Cable Battery Bank s Positive Cable MMP enclosure for single inverter installations includes DC di...

Страница 23: ...vercurrent protection device it can also be used as the required DC disconnect For maximum protection install the circuit breaker or fuse disconnect as near as practical to the batteries If a fuse is...

Страница 24: ...terminal connections Refer to Figures 2 5 and 2 6 for the correct way to connect the DC cables and to stack the hardware Tighten the DC cable connections from 10 to 12 ft lbf 13 6 to 16 3 Nm CAUTION T...

Страница 25: ...e the batteries to access the terminals and vent caps as applicable Also allow at least 1 2 5 cm of space between the batteries to provide good air flow DO NOT mount the batteries directly under the i...

Страница 26: ...h the negative battery cable DC Positive Wire 3 Mount the circuit breaker assembly as near as practical to the batteries and then open the circuit breaker WARNING DO NOT close the DC circuit breaker t...

Страница 27: ...he proper AC wire sizes the inverter s AC input and output wires are required to be protected from short circuits and overloads by an overcurrent protection device and have a means to disconnect the A...

Страница 28: ...e ground terminals remove the two Phillips screws that hold the AC access cover plate to the left side of the inverter see Figure 1 3 Item 15 Each connection on the AC terminal block is rated for 221...

Страница 29: ...t cover Figure 1 3 Item 15 to access the internal AC terminal block Wiring the Inverter AC Input from the main panel 2 a For a 120 240 VAC input Connect the hot 1 wire black from the main panel s dedi...

Страница 30: ...F AC Terminal Block AC input and output wiring AC GROUNDS to from either Panel Note The inverter s AC input output wiring goes through an AC bypass switch assembly when using a MMP enclosure MS PAE In...

Страница 31: ...ou can either use an appropriate buck boost transformer or you can connect to the MS PAE inverter directly Note Be aware that most buck boost transformers are not isolated but are autotransformers whi...

Страница 32: ...C MS PAE SERIES H1 IN N IN H1 OUT H2 IN H2 OUT N OUT 120 VAC 120 VAC 240 VAC Figure 2 10 Connecting the MS PAE to Three Phase Power using a Buck Boost Transformer STEP UP ISOLATION TRANSFORMER 208 VAC...

Страница 33: ...ing electrode system or the grounded conductor This wire or the ends of this wire should be green or green with a yellow stripe or this wire can be bare copper Grounding Electrode Conductor GEC The wi...

Страница 34: ...unding electrode GE for the DC system and the AC system In this method since there are multiple connections to the DC grounding electrode GE the size of the DC grounding electrode conductor GEC DC can...

Страница 35: ...ode conductor is that it is only required to stabilize the system voltage with respect to earth and the other properly sized conductors in each electrical system will safely carry any fault currents i...

Страница 36: ...ther non current carrying exposed metal surfaces in the entire electrical system that may be accidentally energized must be grounded The equipment grounding conductor must be sized to safely carry the...

Страница 37: ...tem Since the RE wires are connected to the conductors coming into the house the inverters charge controllers batteries and other components in the house or power shed are easily susceptible to damage...

Страница 38: ...the Authority Having Jurisdiction AHJ The plaque or directory must provide the location of system disconnecting means and information regarding whether the structure contains a standalone electrical...

Страница 39: ...a 10 watt light bulb to the inverter output and then verify it comes on and shines normally DO NOT connect anything but a light bulb until all wiring and voltages are confirmed to be correct Info The...

Страница 40: ...ature is enabled This feature is provided to conserve battery power when AC power is not required In this mode the inverter pulses the AC output looking for an AC load i e electrical appliance Wheneve...

Страница 41: ...chargers available today When an AC source is connected to the AC input the inverter begins monitoring for acceptable AC voltage Once the inverter has accepted this AC voltage the AC transfer relay cl...

Страница 42: ...at charging The Float Charging stage reduces battery gassing minimizes watering requirements for flooded batteries and ensures the batteries are maintained at optimum capacity Full Charge Battery Save...

Страница 43: ...unstable output may nuisance transfer This commonly happens when powering loads that are larger than the generator can handle causing the generator s output to constantly fall below the inverter s in...

Страница 44: ...matically restart once the battery falls to the HBCI High Battery Cut In level Refer to Table 3 1 to determine the HBCO and HBCI levels for your inverter model Info High battery voltage may be caused...

Страница 45: ...erload over temperature or an internal fault Refer to the Troubleshooting section to help diagnose clear any fault condition Slow Flash blinks on for 4 seconds then off for 4 seconds Indicates the bat...

Страница 46: ...ver discharge and the AC loads from unregulated power brown outs Batt AmpHrs This setting allows the user to establish the battery bank size in amp hours which tells the charger how long to charge the...

Страница 47: ...d to a remote it allows these advanced features to be set up or enabled However the remote may have a later newer software revision than the inverter so some of the features and functionality in the r...

Страница 48: ...capable of being stacked in parallel the models must be identical i e all MS4024PAE models or all MS4448PAE models A maximum of four identical MS PAE inverters can be connected in parallel The ME RTR...

Страница 49: ...0VAC Loads ME RTR required to stack MS PAE inverters in parallel Magnum Accessory Battery Bank ME BMK NS Battery Monitor Magnum Accessory AC GROU ND To Byp ass AC GROU ND L2 OUT L1 OUT L2 IN L1 IN INV...

Страница 50: ...of the neutral and ground conductors to each inverter input The AC output side of a parallel system requires an electrical panel referred to as the inverter panel that combines all the inverter outpu...

Страница 51: ...UNT 1000A 100 M V BATTERY TEMP SENSOR I NV E RTE R D C D IS CO NNE CTS BATTER Y NEGA TIVES To each inverter battery negative terminal TO SYSTEM GROUN D 1 0 AWG 1 0 AWG D C GROUN DS To each inverter DC...

Страница 52: ...grounds are connected and properly installed AC input and output connections are wired correctly to the terminal block and are not reversed double check before turning on the inverters 4 4 1 Power up...

Страница 53: ...ADC P3 INV Home MS4024PAE Slave Inverter Standby 23 4VDC 0ADC P2 INV Home Master Inverter stacked Slave Inverter stacked Standalone Inverter not stacked Figure 4 5 ME RTR Port Master Slave Displays CA...

Страница 54: ...on the inverters are currently disabled off Press and release the INVERTER ON OFF switch on the ME RTR to enable turn on all of the inverters 8 Disconnect the incoming AC power to the inverters Verify...

Страница 55: ...d on the inverter s battery voltage If the battery voltage begins rising the output frequency starts decreasing as the battery voltage returns to its correct voltage level the frequency increases In a...

Страница 56: ...ault occurs when an internal fault is detected An inverter reset is required to clear fault Remove all AC and DC power to the inverter or press and hold down the inverter s power switch for 10 seconds...

Страница 57: ...l stacked inverters If a reset is required perform a hard reset instead see Section 6 1 2 Prior to performing any reset ensure all AC power utility generator shorepower is removed from the inverter s...

Страница 58: ...tput at 25 C 105 ADC 60 ADC Charger efficiency 85 Power factor 0 95 Input current at rated output 15 AAC leg at 120 240 VAC split phase 17 5 AAC leg at 120 240 VAC split phase General Features and Cap...

Страница 59: ...500 3000 3500 4000 4500 Power VA Efficiency Percentage MS4448PAE Efficiency Graph Figure A 2 MS4448PAE Efficiency Chart Figure A 1 MS4024PAE Efficiency Chart A 1 Efficiency Graphs The following curves...

Страница 60: ...e jumper for 12 24 and 48 volt battery banks and a 4 position DIP Dual In line Package switch which provides the ability to change the relay timing configurations to allow compatibility with a wider r...

Страница 61: ...ctive amp hour capacity is reduced When determining the battery requirements needed for the inverter system realize that the battery capacity will be reduced if they will be installed in a climate whe...

Страница 62: ...e calculated load the Total Amp Hours should be multiplied by 1 2 to factor in an average 80 inverter efficiency B 5 Battery Bank Sizing Worksheet Complete the steps below to determine the battery ban...

Страница 63: ...smaller lower voltage batteries In Figure B 3 below four 6 VDC 200 AH batteries are combined into two strings resulting in a 12 VDC 400 AH battery bank Series Parallel Battery Wiring combines battery...

Страница 64: ...H overcurrent protection 12 VDC battery 100 AH to 24 VDC inverter total capacity 200 AH 6 VDC battery 200 AH overcurrent protection 6 VDC battery 200 AH 6 VDC battery 200 AH 6 VDC battery 200 AH Serie...

Страница 65: ...0 Ahrs 6 volt battery 200 AH 6 volt battery 200 AH 6 volt battery 200 AH 6 volt battery 200 AH overcurrent protection 6 volt battery 200 AH 6 volt battery 200 AH 6 volt battery 200 AH 6 volt battery 2...

Страница 66: ...1 Typical Appliance Power Consumption Figure C 1 AC Waveforms TIME VOLTAGE 40 80 0 120 40 160 200 80 120 160 200 Modified Sine Wave Pure Sine Wave Square Wave C 2 Inverter Output Waveforms The inverte...

Страница 67: ...ge Deep Cycle Battery A battery designed to be routinely discharged to 20 of its maximum capacity without damage This type of battery is recommended for use with an inverter system Derating As an inve...

Страница 68: ...rid Shorepower The process of providing shoreside electrical power to a boat while its main and auxiliary engines are turned off The source for shorepower may be grid power from an electric utility co...

Страница 69: ...pon request from Sensata the original purchaser must prove the product s original date of purchase by presenting a dated bill of sale or itemized receipt 5 The original purchaser shall return the prod...

Страница 70: ...MS PAE Series Owner s Manual PN 64 0032 Rev C Magnum Energy Products Manufactured by Sensata Technologies Web www SensataPower com...

Отзывы: