2017 Sensata Technologies
Page 5
Introduction
16
15
13
14
Figure 1-3, Left Side Features
13
Exhaust Air Vents
– ventilation openings that allows heated air to be removed by the
internal cooling fan.
14
Model/Serial Number Label
–
includes model/serial number information, date of
manufacture, and inverter and charger speci
fi
cations. See the
MS-PAE Speci
fi
cations
in Appendix A for more information and the different models available.
15
AC Access Cover
– provides access to the internal AC wiring terminal block. This terminal
block is used to hardwire all inverter AC input and output wiring connections. Remove the
two screws to access the AC wiring terminal block.
16
Input Circuit Breakers (CB1 and CB2)
– these circuit breakers protect the unit’s
internal wiring and pass-thru relay on each input (L1 and L2)—while in the standby mode.
These input circuit breakers are not branch-circuit rated. These circuit breakers pop out
when they open. Press in to reset power capacity.
CAUTION:
Circuit breakers that are branch-circuit rated must be installed in the
inverter’s input and output wiring.
CAUTION:
The inverter’s internal AC transfer relay is rated for 30 amps per leg. The
pass-thru current must be no greater than 30 amps per leg, or damage to the relays
may occur.
AC Access
Cover
Model/Serial
Number Label
Exhaust
Air Vents
(back side and
on right side)
Input Circuit
Breakers