Operation
6.0 Troubleshooting
The remote may not be functioning correctly, use the following table to help
fi
nd a solution.
Table 6.1, Remote Troubleshooting
Symptom
Possible Cause
Solution
LCD text
display is
locked-up,
pushing any
pushbutton
has no
response
- may show
“revision” or
“connecting”.
RJ11 connections on
communication cable
are not making a
good connection
Reset remote
: 1) disconnect
remote cable from inverter for 5
seconds and reconnect; 2) check
RJ11 cable connection on back
of remote (see
fi
gure 2-2).
Important: ensure the RJ11
connector is pushed into the
correct port; you should feel/
hear “click” when the connection
is made.
Remote not getting
suf
fi
cient power from
inverter.
Ensure inverter batteries are
connected and inverter is
operating correctly; inverter
should be able to invert and
power AC loads from batteries
(ensure no AC power is
connected to the inverter AC
inputs).
LEDs and
backlight are
off.
Remote is in Power
Saver mode.
Press any button to reactivate
remote (or turn Power Saver
mode Off).
Remote is
non-functional
(no lights, no
text on LCD
display and no
response when
pressing any
pushbutton).
Communication
cable bad or not
correctly connected
to remote port on
inverter.
Check communications cable
from inverter to remote;
ensure: 1) it is connected to
the REMOTE port, 2) the correct
communications cable is used
(a 4-conductor telephone
cable may be substituted to
determine if cable is good).
Inverter is not
connected to
batteries.
Ensure inverter batteries are
connected and inverter is
operating correctly without
any AC power connected (can
invert and power AC loads from
batteries).