Magnum Energy ME-MR Series Скачать руководство пользователя страница 14

12 

©2009 Magnum Energy Inc.

Setup

 

SETUP: 05 Charge Rate - 

Used to set the maximum charge rate 

allowed to charge the batteries during bulk, absorption, 

fl

 oat and equalize 

charging. Selections are ‘Max Charge = 10%’ up to ‘Max Charge = 100%. 

The 

Max Charge = 10% 

setting is available to help minimize charging while 

continuing to allow pass-thru power. 

The 

Max Charge 

selections are provided as a percentage of the inverter/

charger’s maximum charging capability. Refer to label on the side of the 

inverter or the operator’s manual for the inverter/charger to determine its 

maximum charge rate. Once you 

fi

 nd this maximum charge rate, determine 

the percentage needed to limit the charge rate to your battery bank.

For example, if the maximum charge rate of your inverter/charger is 100 amps 

and you need to limit the charge rate to 50 amps, choose the 

Max Charge = 

50%

 selection (50 amps = 50% of 100 amps).

Default setting:

 Max Charge = 100%

Info:

 The topology of the Magnum inverter, when connected to an 

AC source, will override the setting and start charging if the battery 

voltage is <7 VDC (12 VDC models), <14 VDC (24-volt models) or 

<28 VDC (48-volt models).

How do I determine where to set my maximum charge rate? 

The 

maximum charge rate is generally set to a C/5* rate (C = the total amp-

hour capacity of the battery bank - using the 20-hour AH rate). The C/5 rate 

is usually used when the objective is to charge the batteries as quickly as 

possible (i.e. 400 AH ÷ 5 = 80 amp maximum charge rate). A lower rate such 

as C/20* is used when the batteries need to be charged as slow as possible. 

The ME-MR provides 3 settings for charge rate adjustment and they are 10, 50 

and 100%; multiply this percentage and the max charge rate of the inverter 

to 

fi

 nd the closest setting to the desired charger output. 

CAUTION:

 The C/5 or C/20 charge rate settings are guidelines; they 

are not requirements on how you should set your battery charge 

rate. For speci

fi

 c charge rate requirements, refer to your battery 

manufacturer.

Info:

 If multiple inverter/charger’s are used on a single battery bank, 

you must ensure that the total charge rate from all inverter/chargers 

is limited to the maximum charge rate needed for your battery bank. 

This Charge Rate setting only limits the charging on each inverter/

charger individually, not on all inverter/chargers.

* C/5 or C/20 rate - Charge rates are commonly expressed as a ratio of the total 

amp-hour (AH) capacity of the battery bank. For example, with a 400 AH battery 

bank (C = 400), the C/5 charge rate is 80 A (400/5 = 80 A).

Bottom  line show s 

current “saved” setting

If this setting is correct , press  

men u button to access 

different m enu item s

If a different setting is 

required: 

CHG RATE

100 %

.......

press

press

press

T o save the current 

setting displayed :

CHG RATE

10 %

CHG RATE

50 %

.......

CHG RATE

100%

O N / O F F

C H A N G E

M EN U

H O M E

SA VE

H O L D

Figure 3-5, SETUP: 05 Charge Rate Selections

Содержание ME-MR Series

Страница 1: ...Owner s Manual for Revision 1 0 or higher ME MR Inverter Remote Control www aarrss com...

Страница 2: ...roduct Read all instructions and safety information contained in this manual before installing or using this product All electrical work must be performed in accordance with local state and federal el...

Страница 3: ...Panel Features 2 Figure 2 3 Remote Control Connections 5 Figure 4 1 Inverter Charger Menu Map 18 Figure 6 1 Performing an Inverter Reset 36 Table of Tables Table 3 1 Battery AmpHrs to Absorb Charging...

Страница 4: ...igher see the TECH 02 Revisions display on page 16 for information on how to determine your revi sion level Figure 1 1 Front Panel Features The ME MR is equipped with the following features LED Indica...

Страница 5: ...the conductors passing through walls bulkheads or other structural members are protected to minimize insulation damage such as chafing which can be caused by vi bration or constant rubbing Installing...

Страница 6: ...tion for Flush mounting the remote cutout a mounting hole measuring 2 3 8 x 2 3 8 Mount the remote into the cutout and use the remote to mark and predrill 2 holes for the 6 x 1 2 phillips flat head mo...

Страница 7: ...appear with a system status message indicating the current state of the inverter charger If not please refer to the troubleshooting section The remote is ready for setup Info All power to operate the...

Страница 8: ...complete map of the inverter charger menu items and adjustable settings Familiarize yourself with the items on the front panel which are used to find adjust and save the desired setting They are LCD D...

Страница 9: ...gers Default setting Shore Max 30A Where to set Set the Shore setting to match the current rating of the utility power or generator s circuit breaker If using multiple AC sources utility and generator...

Страница 10: ...However if you require some small load i e digital clocks satellite receivers answering machines etc to always be on then this feature should be turned off Search Off I want to use the Search watts f...

Страница 11: ...specifically made for continuous use Deep cycle batteries are rated either by a amp hours or b reserve capacity in minutes Amp hour AH capacity is a measurement of how many amps a battery can deliver...

Страница 12: ...se the voltage of the battery bank but the amp hour rate remains the same For example You have a 12 volt battery bank with two 6 volt batteries that are rated at 220 amp hours The positive terminal of...

Страница 13: ...ype to Charge Voltages Battery Type Inverter Voltage Absorption Voltage Float Voltage Equalization Voltage GEL 12 VDC 14 1 VDC 13 6 VDC 14 1 VDC1 24 VDC 28 2 VDC 27 2 VDC 28 2 VDC1 48 VDC 56 4 VDC 54...

Страница 14: ...is usually used when the objective is to charge the batteries as quickly as possible i e 400 AH 5 80 amp maximum charge rate A lower rate such as C 20 is used when the batteries need to be charged as...

Страница 15: ...do I set the LBCO setting If you want to cycle the batteries slightly but don t want to discharge them more than 20 then the LBCO setting should be set from 11 VDC 12 volt models 22 VDC 24 volt models...

Страница 16: ...ng as the AC source The settings not only look at the incoming voltage to determine when to transfer but also determines the response sensitivity to incoming voltage fluctuations Use a VAC Dropout set...

Страница 17: ...current setting displayed PWR SAVE Off PWR SAVE On ON OFF C H A N G E M EN U H O ME SA VE H O L D SETUP 09 Equalize This setting allows you Equalize the batteries after a Float Charge is achieved Equ...

Страница 18: ...ues Scroll to the end of the SETUP menus until TECH Press ON appears Push the ON OFF Change button to access the tech menus Continue to press the ON OFF Change button to see more tech menus TECH 01 Te...

Страница 19: ...earch 5W 03 Batt AmpHrs Batt Amphrs 400 AmpHrs Absorb Time 90 minutes 04 Battery Type BatType Flooded 05 Charge Rate Max Charge 100 06 Low Battery Cut Out LBCO 10 VDC 12 volt models 20 0 VDC 24 volt m...

Страница 20: ...0 0 Xfm Temp xx C Bat Temp xx C FET Temp xx C M odel xxxx M EN U H O ME LEGEN D D efault selection S elects setup and tech m enus Turns Inverter On Off S aves selection in setup m enu S crolls through...

Страница 21: ...s come on as it goes through a self test Once the self test is complete the LED s along with the LCD provide the operating status of the inverter charger See section 5 3 4 for the LED Indicator Guide...

Страница 22: ...press the MENU pushbutton until the desired selection appears 5 1 7 Home Pushbutton Home Holding down on the Home button for 5 seconds exits SETUP menus and returns to the status screen 5 1 8 Hold Bu...

Страница 23: ...and in Inverter Standby do not press the ON OFF pushbutton to turn the inverter function off If the green INV LED is off inverter power will NOT be available to run your critical loads if the externa...

Страница 24: ...mode which means the AC loads on the inverter output are less than the SETUP 01 Search watts setting The search mode function is used to reduce the inverter draw from the battery and may be turned of...

Страница 25: ...than this voltage the charger will skip the Bulk and Absorb charging stages and go directly to Float Charging Bulk Charging The battery charger is delivering maximum current determined by the SETUP 05...

Страница 26: ...rcharging thus preventing excessive loss of water in flooded batteries or drying out of GEL AGM batteries After 4 hours Float Charging the charger will turn off and Full Charge is displayed charger is...

Страница 27: ...s should be equalized periodically ranging anywhere from once a month to once or twice per year Other experts only recommend equalizing when the cells have a low specific gravity or when the differenc...

Страница 28: ...s or 50 0 VDC 48 volt models Remedy This fault will also automatically restart if AC power such as utility shore power or a generator is connected to the inverter charger s input and battery charging...

Страница 29: ...output has exceeded the inverters AC current protection limits If the overload condition lasts for less than 10 seconds the unit will automatically restart and resume operation However if the overload...

Страница 30: ...ens the fault will automatically restart Remedy Check the DC voltage on the inverter s DC terminals and compare it with the DC voltage on the battery bank these two volt ages should be very close 0 5...

Страница 31: ...fault causes the inverter to shutdown to protect internal power components and may be caused by an excessive AC load If the overload condition lasts for less than 10 seconds the unit will automatical...

Страница 32: ...power transformer from damage When the TCO has cooled down the inverter will automatically restart and resume operation Remedy If this fault occurs while inverting reduce load on the inverter If it o...

Страница 33: ...tiple inverters in a stacked configuration If this occurs perform an inverter reset see section 6 2 Stack Mode Fault This unit has detected a problem with the other stacked inverter check that unit fo...

Страница 34: ...facility Bridge This fault message displays and the inverter shuts down because the internal power bridge protection circuit has been activated Charger This fault message displays and the inverter shu...

Страница 35: ...e inverter will automatically supply AC power to the loads if shore or generator power is lost BLINKING Inverter is in search mode the AC load is below the SETUP 01 Search Watts setting FAULT red OFF...

Страница 36: ...e inverter batteries are connected and inverter is operating correctly inverter should be able to invert and power AC loads from batteries ensure no AC power is connected to the inverter AC inputs LED...

Страница 37: ...Bulk Charging or Absorb Charging Check the DC amps meter and DC voltmeter on the ME MR display it should be 80 or more of rated charge current if the battery voltage is under 14 0 VDC 28 0 VDC on 24 v...

Страница 38: ...N OFF pushbutton The Status LED will go off after the pushbutton is released After the inverter reset is completed press the ON OFF pushbutton to turn the inverter ON Some older inverter models do not...

Страница 39: ...h value of the product at the time the original purchaser returns the product for repair determined by the price paid by the original purchaser Magnum Energy shall not be liable for any other losses o...

Страница 40: ...Magnum Energy Inc 2211 West Casino Rd Everett WA 98204 Phone 425 353 8833 Fax 425 353 8390 Web www magnumenergy com PN 64 0031 Rev A...

Отзывы: