Page 42
©
2020 Sensata Technologies
Operation
3.7 Factory Default Values
The MSH3012RV inverter/charger uses default values for the adjustable settings (shown in Table
3-2) that are adequate for most installations. If some of the operating parameters need to be
changed from the default values, an optional remote control/display can be used to make those
changes. To determine if you need a remote display, information on the inverter/charger settings
that can be changed is provided below. Once programmed, the settings are saved in the remote’s
non-volatile memory and are preserved until changed—even if DC power to the inverter is lost
(as long as the remote is connected). See Section 3.9 for additional information.
For information on the full range of settings for each function in your remote, refer to its owner’s
manual at
www.SensataPower.com
.
• Shore
Max/Input
Amps:
This setting ensures the inverter AC loads receive the maximum
current available from shorepower or a generator. When the total current used to power the
AC loads and charge the batteries begins to approach the
Shore Max/Input Amps
setting,
the current that was used for charging the batteries will automatically be reduced.
• Search
Watts:
This setting allows you to turn off the power-saving Search mode circuitry,
or to adjust the power level at which the inverter will “wake up” and start inverting.
• LowBattCutOut:
This setting determines when the inverter will turn off based on low
battery voltage. The inverter turns off automatically after the battery voltage has been
below this setting for more than one minute. This protects the batteries from over-discharge
and the AC loads from unregulated power (brown-outs).
• Absorption
Time:
This setting allows the user to determine how long to charge the batteries
in the Absorb Charge stage.
• Battery
Type:
Sets the type of batteries being used in the system. This information tells
the charger what voltage level to use to charge the batteries.
• Charge
Rate:
This setting can be used to turn off the charger, limit the amount of current
that the charger can use (leaving more current available to power loads), or to ensure small
battery banks are not overheated because of a charge rate that is too high.
• VAC
Dropout:
Sets the minimum AC voltage that must be present on the AC input before
the unit transfers from Standby mode to Inverter mode. This protects the AC loads from
shorepower outages and brown-outs.
Using a remote display also allows you to enable an equalize charge for certain battery types,
displays inverter/charger’s operating status, and provides fault information for troubleshooting.
The table below provides the inverter’s default settings—without a remote control connected.
If a remote is connected, the remote settings are saved in the inverter—even if the remote is
disconnected—until all power to the inverter is removed.
Table 3-2, Inverter/Charger Default Values
Adjustable Settings
Default Values
Shore Max/Input Amps
50 Amps
Search Watts
5 Watts
LowBattCutOut
10 VDC (one min. delay), 8.5 VDC (no delay)
Absorption Time
600 AmpHrs (Absorb Time = 120 minutes)
Battery Type
Flooded – Liquid Lead Acid:
Absorb = 14.6 VDC, Float = 13.4 VDC
Charge Rate
100%
VAC Dropout
80 VAC (input 1) / 80 VAC (input 2)