16
6.2
Current Output
P10:
Value (of distance, level, volume or flow) assigned to 4 mA current output
P11:
Value (of distance, level, volume or flow) assigned to 20 mA current output
Values are interpreted according to
P01(a)
. Please note that in case of programming for (LEV or VOL) % measurement the
min and max value has to be entered in the relevant engineering units of LEV (m, ft) or VOL (m
3
, ft
3
).
Assignment can be made so that the proportion between the change of the (measured or calculated) process value and the
change of the current output be either direct or inverse. E.g. lev 1m assigned to 4mA and lev 10m assigned to 20mA
represents direct proportion and lev 1m assigned to 20mA and lev 10 m assigned to 4mA represents the inverse proportion.
FACTORY DEFAULT:
P10 0 level (max distance)
P11 max level (min distance)
P12: - - - a Error indication by the current output
In case of error the Echotel will provide one of the current outputs below. (For errors and their indications see Chapter 7).
a
Error indication (according to NAMUR)
0
Hold last value
1
3.6 mA
2
22 mA
FACTORY DEFAULT: 0
6.3 Relay O
utput
P13: - - - a Relay function
a
Relay function
Also set:
0
DIFFERENTIAL LEVEL CONTROL
(Hysteresis control)
Relay is energised if the measured or
calculated value exceeds the value set in
P14
Relay is de-energised if the measured or
calculated value descends under the value
set in P15
Relay
Level
P14
P15
Time
Energised:
De-energised:
P14, P15
There is a need
to set (in level
min 20mm)
hysteresis
between P14 and
P15
1
Relay is energised in case of Echo Loss
-
2
Relay is de-energised in case of Echo Loss
-
3
COUNTER
Used for open channel flow metering.
A 140 msec pulse is generated every 1, 10,
100, 1.000 or 10.000 m
3
according to P16.
P16= 0: 1m
3
P16= 1: 10 m
3
P16= 2: 100 m
3
P16= 3: 1.000 m
3
P16= 4: 10.000
m
3
FACTORY DEFAULT: 2
P14: …
Relay parameter – Setpoint value
FACTORY DEFAULT: 0
P15: …
Relay parameter – Setpoint value
FACTORY DEFAULT: 0
P16: …
Relay parameter – Pulse rate
FACTORY DEFAULT: 0