10
5.2.4 Current Output Scaling
This programming mode is the simple and fast way to modify the scaling of the current
output.
For changing all parameters other than those assigned to 4 and 20 mA use either the QUICKSET
(5.2.2). or the Full Parameter Access (5.2.3).
Current Output Scaling mode is useful for re-scaling i.e. for modifying of the minimum and
maximum level assigned to the output signals 4 and 20 mA, if other than the factory default.
Current Output Scaling is aided by 2 screens for setting.
The instructions for this programming can also be found below the screw cover on the front panel
of the Echotel.
Note: For this programming the Echotel has to be in level measurement mode. See chapter 6.1
(P01)
.
Keys
Function
ENTER
E
+ UP
(press for 3
seconds)
Enter or exit Current Output Scaling programming mode
UP
/ DOWN
Increase/decrease blinking digit or scroll up/down
NEXT
Move left with the blinking digit
UP
+ DOWN
"GET LEVEL" - display actual level value measured by the Echotel
ENTER
E
Save actual value on the screen and move to the next screen
NEXT
+ UP
Quit Current Output Scaling without saving the modifications
NEXT
+ DOWN
Display Factory Default of the relevant screen
Screens
Actions
4 represents the output signal
x = level value to be assigned
4
mA
xxxx
:– level value assigned to 4 mA current output
Manual: set required value
(by UP
/ DOWN
/
NEXT
keys)
and save it
(by the key
ENTER
E
)
Automatic: use the “GET LEVEL” function
(UP
+ DOWN
)
to obtain actual measured value
with level in
tank or a fix target, e.g. wall. (“GET LEVEL” functions only if ECHO LED is lit) and save
it as above.
DEFAULT: 0 m (0%, Empty tank)
20 represents the output signal
x = level value to be assigned
20
mA
xxxx
:
– Level value assigned to 20 mA current output
Manual: set required value
(by UP
/ DOWN
/
NEXT
keys)
and save it
(by the key
ENTER
E
)
Automatic: use the “GET LEVEL” function
(UP
+ DOWN
)
to obtain actual measured value
with level in tank or a fix target, e.g. wall. (“GET LEVEL” functions only if ECHO LED is lit) and
save it as above.
DEFAULT: max. level = max. measuring distance - dead band (100%, Full tank) See chapter 5.1
(P04, P05)
4
:
xxxx
20
:
xxxx