48-635 E3 Modulevel
®
Displacer Level Transmitter
2.6.5.1
Measurement Type: Level Only: Factory (display only) or User Calibration sub-menu
Display
Action
Comment
1
LVDT%
xx.xx %
Diagnostic display
2
Calib SG
x.xxx sg
Factory set
Factory calibration menu only
3
DrySensr
xx.xx %
Enter or capture sensor
output for Dry Sensor
Press
and
simultaneously to capture current
sensor output
4
SnrCalLo
xx.xx %
Enter or capture sensor
output for Low Cal Point
Press
and
simultaneously to capture current
sensor output
5
LvlCalLo
xx.xx lu
Enter Level value
corresponding to SnrCalLo
6
Set 4mA
xx.xx lu
Enter the level value for
4 mA set point
Specify level at 4 mA (User Cal menu only)
7
SnrCalHi
xx.xx %
Enter or capture sensor
output for High Cal Point
Press
and
simultaneously to capture current
sensor output
8
LvlCalHi
xx.xx lu
Enter Level value
corresponding to SnrCalHI
9
Set 20mA
xx.xx lu
Enter the level value for
20 mA set point
Specify level at 20 mA (User Cal menu only)
10
Escape
Press
to exit Calibration
sub-menu; Returns to
Factory Menu
Display
Action
Comment
38a
Factory Cal
Menu
Press
to display the
Factory Calibration sub-menu
CalSelct = Factory
Submenu on page 19
38b
User Cal Menu
Press
to display the User
Calibration sub-menu
CalSelct = User
Submenu below
39
AdjSnrLo
Diagnostic Display
40
AdjSnrHi
Diagnostic Display
41
Conv Fct
xxxx
Diagnostic Display
42
Scl Ofst
xxx
Diagnostic Display
43
LVDT%
xx.xx %
Diagnostic Display
44
Chan 0
Diagnostic Display
45
Chan 1
Diagnostic Display
46
NSP Value
Diagnostic Display
47
ElecTemp
xxx F
Diagnostic Display
Present temperature in electronics compartment
48
Max Temp
xxx F
Diagnostic Display
Maximum electronics temperature recorded
49
Min Temp
xxx F
Diagnostic Display
Minimum electronics temperature recorded
2.6.5.1
Measurement Type: Level Only (cont.)