Torque Detection
The overtorque detection circuit activates when the motor load causes the motor current to exceed
the overtorque detection level (L6-02). When an overtorque condition is detected, alarm signals can
be sent to a multi-function output. To output an overtorque detection signal, select torque detection 1
at either of the multi-function contact outputs (H2-XX=”B” or “17”).
Note:
•
To detect overtorque/undertorque during acceleration or deceleration, set to “2” or
“4” / “6” or “8”.
•
To continue operation after overtorque/undertorque detection, set to “1” or “2” / “5”
or “6” During detection, the digital operator displays an “OL3” alarm (blinking).
•
To stop the inverter after an overtorque/undertorque detection fault, set to “3” or “4”
/ “7” or “8”. During detection, the digital operator displays an “OL3/UL3” fault.
Parameter
Code
Display
Function
Range
Initial
Value
Access
Level
L6-01
Torque Det 1 Sel
Activates overtorque/
undertorque detection and
selects whether detection
generates an alarm or a fault
0
Adv
0
Disable
1
OT At Speed Agree–
Alarm
2 OT
At
Run–Alarm
3
OT At Speed Agree–
Fault
4
OT At Run–Fault
5
UT At Speed Agree–
Alarm
6
UT At Run–Alarm
7
UT At Speed Agree–
Fault
8
UT At Run–Fault
Table 5-9:
Setting
Description
0
Torque detection is disabled (
factory default
).
1
Overtorque detection is enabled whenever at the speed agree level (when inverter is not accelerating or
decelerating). Continue running after detection (OT1 alarm).
2
Overtorque detection is enabled always. Continue running after detection (OT1 alarm).
3
Overtorque detection is enabled whenever at the speed agree level. Coast to a stop after detection (OT1
fault).
4
Overtorque detection is enabled always. Coast to a stop after detection (OT1 fault).
5
Undertorque detection is enabled whenever at the speed agree level (when inverter is not accelerating
or decelerating). Continue running after detection (UT1 alarm).
6
Undertorque detection is enabled always. Contnuing running after detection (UT1 alarm).
7
Undertorque detection is enabled whenver at the speed agree level. Coast to a stop after detection (UT1
fault).
8
Undertorque detection is enabled always. Coast to stop after detection (UT1 fault)
Содержание IMPULSE VG+ Series 3
Страница 1: ...Software 8001 X July 2005 Part Number 140 10257 Copyright 2005 Magnetek Instruction Manual...
Страница 6: ...c h a p t e r 1 Introduction...
Страница 7: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 1 2 This page intentionally left blank...
Страница 14: ...c h a p t e r 2 Installation...
Страница 15: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 2 2 This page intentionally left blank...
Страница 23: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 2 10 This page intentionally left blank...
Страница 24: ...c h a p t e r 3 Wiring...
Страница 25: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 3 2 This page intentionally left blank...
Страница 40: ...c h a p t e r 4 Programming Basic Features...
Страница 41: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 4 2 This page intentionally left blank...
Страница 54: ...c h a p t e r 5 Programming Advanced Features...
Страница 55: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 5 2 This page intentionally left blank...
Страница 149: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 5 96...
Страница 150: ...Troubleshooting IMPULSE VG Series 3 c h a p t e r 6...
Страница 151: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 6 2 This page intentionally left blank...
Страница 170: ...A p p e n d i x A IMPULSE VG Series 3 Parameter Listing...
Страница 171: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 A 2 This page intentionally left blank...
Страница 183: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 A 14...