IMPULSE®•G+ & VG+ Series 3 to Series 4 Transition Guide August 2011
Page 35 of 54
Magnetek, Inc.
Product Transition Guide
IMPULSE
®
•G+ & VG+ Series 4
UL3 Stop Method
C3-08
4
C3-08
4
0: Decel/Alarm (no
further raise
allowed)
0: Decel/Alarm
1: Coast/Alarm (no
further raise
allowed)
1: Coast/Alarm
2: Use B3-03 /Alarm
(no further raise
allowed)
2: Use B3-03/
Alarm
3: Decel/Fault
3: Decel/Fault
4: Coast/Fault
4: Coast/Fault
5: Use B3-03/Fault
5: Use B3-03/Fault
For setting 0, 2, 3,
5, deceleration is by
B5-08.
For setting 0, 2, 3,
5, deceleration is
by B5-08.
Phantom Stop
Method
C3-09
1
C3-10
1
0: Decel to Stop
0: Decel to Stop
1: Coast to Stop
1: Coast to Stop
2: Use B3-03
Method
2: Use B3-03
Method
Load Share Lim
C3-10
(VG+ only)
0
C3-11
(VG+ only)
1
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Klixon Action
C3-11
0
C3-12
0
0: Use B3-03
Method
0: Use B3-03
Method
1: Allow Lower Only
1: Allow Lower
Only
UL2 Revolutions
C3-12
(VG+ only)
0 Revs
C3-16
(VG+ only)
0 Revs
--
UL1 Revolutions
C3-13
(VG+ only)
0 Revs
C3-17
(VG+ only)
0 Revs
--
LL1 Revolutions
C3-14
(VG+ only)
0 Revs
C3-18
(VG+ only)
0 Revs
--
LL2 Revolutions
C3-15
(VG+ only)
0 Revs
C3-19
(VG+ only)
0 Revs
--
Load Float Time 2
C4-01
(VG+ only)
10 sec
C4-01
(VG+ only)
10 sec
--
Load Float Gain
C4-02
(VG+ only)
Drive
Dependent
C4-02
(VG+ only)
5
--
Load Float Count
C4-03
(VG+ only)
10
C4-03
(VG+ only)
10
--
Load Check 0/1
C5-01
0
C5-01
0
0: Disabled
0: Disabled
1: Enabled
1: Hold & Measure
--
3: Immediate
--
9: Setup
LC Alarm Action
C5-02
4
C5-02
4
0: Alarm Only
0: Alarm Only
1: Decel to Stop
1: Decel to Stop
2: Coast to Stop
2: Coast to Stop
3: Fault Stop
3: Fault Stop
4: Use B3-03
Method (allows
Lower only)
4: Use B3-03
Method (allows
Lower only) (alarm)
Parameter
Name
Series 3
Series 4
Comments
No.
Default
No.
Default
Series 3
Series 4