A1-1
The GPD 315 control circuits use various parameters to select functions and characteristics of the
GPD 315. Changing of parameter settings must be done in the Program mode, or by use of the
Function LEDs, if available (see Section 4).
The following table lists all parameters in numerical order. For each parameter, reference
paragraph(s) in Section 5 are listed (if applicable) where the features of the GPD 315 affected by
that parameter are described.
Table A1-1. GPD 315 Parameters
Appendix 1. LISTING OF PARAMETERS
SETTING RANGE
SETTING
FACTORY
USER
PARA.
CONSTANT
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0: n001 can be read and set;
n002 - n179
read only
1: n001 - n049 can be read and set
2: n001 - n079 can be read and set
3: n001 - n119 can be read and set
Parameter Selection /
4: n001 - n179 can be read and set
Initialization
5: Not Used
1
1
5.21
6: Clear Fault History Only
7: Not Used
8: 2-wire Initialization (Jap Spec.)
9: 3-wire Initialization (Jap Spec.)
10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)
Control Method Selection
0: V/f Control
1
0
2.1
1: Open Loop Vector
0: Digital Operator
Operation Method Selection
1: Terminal
1
1
5.13
2: Serial Communication (Modbus)
3: Option Card
0: Digital Operator Pot
1: Digital Operator
2: Voltage Reference (0 to 10V)
3: Current Reference (4 to 20 mA)
Reference Selection
4: Current Reference (0 to 20 mA)
5: Pulse Train Reference
1
2
5.13
6: Serial Communications (Modbus)
7: Multi-Function Analog Input (0 to 10V)
8: Multi-Function Analog Input (4 to 20 mA)
9: Option Card
Stop Method
0: Ramp to stop
1
0
5.24
1: Coast to stop
n006
Reverse Prohibit
0: Reverse Run enabled
1
0
1: Reverse Run disabled
0: STOP key is effective regardless of
programming of n003
STOP
Key Function
1: STOP key is effective only when sequence
1
0
5.13
command (per n003) is from Digital Operator
0: Frequency Reference from digital
Reference Selection -
operator pot
1
0
5.13
Digital Operator
1: Frequency Reference from n024
0: ENTER key must be pressed to write-in
Frequency Reference Setting
new value
1
0
5.13
Method From Digital Operator 1: ENTER key does not have to be pressed
to write-in new value
Operation Selection
0: Disabled (operation continues)
When Digital Operator is
1: Enabled (motor coasts to a stop and fault
1
0
5.15
Disconnected
is displayed)
Frequency - Max.
50.0 to 400.0
0.1 (Hz)
60
Voltage - Max.
0.1 to 255.0 (230V drive)
0.1 (V)
230
0.2 to 510.0 (460V drive)
460
Frequency - Max.
0.2 to 400.0
0.1 (Hz)
60
Voltage Point
Frequency - Midpoint
0.1 to 399.9
0.1 (Hz)
Note 2
5.25
Voltage - Midpoint
0.1 to 255.0 (230V drive)
0.1 (V)
Note 2
0.2 to 510.0 (460V drive)
Frequency - Min.
0.1 to 10.0
0.1 (Hz)
Note 2
Voltage - Min.
0.1 to 50.0 (230V drive)
0.1 (V)
Note 2
0.2 to 100.0 (460V drive)
Содержание GPD 315
Страница 1: ...GPD 315 Technical Manual Magne Tek ...
Страница 20: ...1 14 ...
Страница 32: ...3 2 ...
Страница 76: ...5 40 PID Block Diagram ...
Страница 80: ...5 44 ...
Страница 96: ...A1 8 ...
Страница 100: ...A3 2 ...
Страница 102: ...A4 2 ...
Страница 110: ...A6 6 ...
Страница 114: ......
Страница 116: ......