6-7
Fault Display
Digital
RUN (Green)
Drive
Explanation
Causes and
Operator
ALARM (Red)
Status
Corrective Actions
CPF-05
Cycle power.
A/D converter fault is
If the fault remains,
detected.
replace the drive.
CPF-06
Remove power to the
Option card connecting fault
drive.
Check the connection
Protective
of the digital operator.
Operation.
CPF-07
Cycle power after checking
Output is
Operator control circuit
the digital operator is
shut OFF
(EEPROM or A/D
securely mounted.
and motor
converter) fault
If the fault remains,
coasts to
replace the digital operator
a stop.
or drive.
OPR (Operator
Cycle power.
connecting fault)
If the fault remains,
replace the drive.
CE (MODBUS
Check the communication
communications fault)
devices or communication
signals.
STP (Emergency stop)
Check the external circuit
The drive stops
(sequence).
according to parameter
n005 after receiving the
emergency stop fault
signal.
Stops
according to
• Insufficient power
Check the following:
parameter
supply voltage
• Power supply voltage
• Control power supply
• Main circuit power
fault
supply wiring is
• Hardware fault
connected.
• Terminal screws are
securely tightened.
• Control sequence.
Replace the drive.
Table 6-2. Fault Displays and Corrective Actions - Continued
For display/clear of fault history, refer to page 4-4.
or
__
(OFF)
Содержание GPD 315
Страница 1: ...GPD 315 Technical Manual Magne Tek ...
Страница 20: ...1 14 ...
Страница 32: ...3 2 ...
Страница 76: ...5 40 PID Block Diagram ...
Страница 80: ...5 44 ...
Страница 96: ...A1 8 ...
Страница 100: ...A3 2 ...
Страница 102: ...A4 2 ...
Страница 110: ...A6 6 ...
Страница 114: ......
Страница 116: ......