Current Ratings & Horsepower Range
RATED
CURRENT
NOMINAL
MODEL
INPUT
RATING (AMPS)
HORSEPOWER
NO.
0.8
1/8
MVA001
1.6
1/4
MVA002
2
3.0
1/2
MVA003
3
5.0
3/4 & 1
MVA005
0
8.0
2
MVA008
V
11.0
3
MVA011
17.5
5
MVA017
25
7.5
MVA025
33
10
MVA033
1.2
1/2
MVB001
4
1.8
3/4
MVB002
6
3.4
1 & 2
MVB003
0
4.8
3
MVB005
V
9.2
5
MVB009
14.8
7.5
MVA015
18
10
MVA018
WARNING
Do not touch circuit components until main input power has been turned
OFF. Status indicator LEDs and Digital Operator display will be extinguished
when the DC bus voltage is below 50 VDC. Wait at least one additional
minute.
Do not connect or disconnect wires and connectors while the main input
power is turned on.
CAUTION
The GPD 315 leaves the factory with parameters initialized for 2-Wire control
(when using external Run/Stop signals). Before using the initialization
function of constant
n001 , know your control wiring configuration:
8 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
9 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)
Entering either Initialization code resets all parameters to factory settings,
and automatically returns parameter
n001 setting to “ 1 ”. If the GPD 315 is
connected for 3-Wire control and this parameter is set to “ 8 ” (2-Wire
Control Initialization), the motor may run in reverse direction WITHOUT A
RUN COMMAND APPLIED. Equipment damage or personal injury may
result.
Data subject to change without notice.
Содержание GPD 315
Страница 1: ...GPD 315 Technical Manual Magne Tek ...
Страница 20: ...1 14 ...
Страница 32: ...3 2 ...
Страница 76: ...5 40 PID Block Diagram ...
Страница 80: ...5 44 ...
Страница 96: ...A1 8 ...
Страница 100: ...A3 2 ...
Страница 102: ...A4 2 ...
Страница 110: ...A6 6 ...
Страница 114: ......
Страница 116: ......