6-6
Fault Display
Digital
RUN (Green)
Drive
Explanation
Causes and
Operator
ALARM (Red)
Status
Corrective Actions
EF
¨
Check the external circuit
(External fault)
(sequence).
Drive receives an
external fault input from
control circuit terminal.
EF0: External fault
reference through
MODBUS
communications
EF1: External fault
input command from
control circuit
terminal S1
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
Protective
command from control
Operation.
circuit terminal S4
Output is
EF5: External fault input
shut OFF
command from control
and motor
circuit terminal S5
coasts to
EF6: External fault input
a stop.
command from control
circuit terminal S6
EF7: External fault input
command from control
circuit terminal S7
CPF-00
Cycle power after checking
Drive cannot
the digital operator is
communicate with the digital
securely mounted.
operator for 5 sec. or
If the fault remains,
more when power is
replace the digital operator
turned ON.
or drive.
CPF-01
Cycle power after checking
Transmission fault
the digital operator is
occurred for 5 sec or more
securely mounted.
when transmission starts
If the fault remains,
with the digital operator.
replace the digital operator
or drive.
CPF-04
• Record all parameter
EEPROM fault of drive
data and initialize the
control circuit is detected.
constants. (Refer to
paragraph 5.__ for
constant initialization.)
• Cycle power.
If the fault remains,
replace the drive.
Table 6-2. Fault Displays and Corrective Actions - Continued
Содержание GPD 315
Страница 1: ...GPD 315 Technical Manual Magne Tek ...
Страница 20: ...1 14 ...
Страница 32: ...3 2 ...
Страница 76: ...5 40 PID Block Diagram ...
Страница 80: ...5 44 ...
Страница 96: ...A1 8 ...
Страница 100: ...A3 2 ...
Страница 102: ...A4 2 ...
Страница 110: ...A6 6 ...
Страница 114: ......
Страница 116: ......