background image

 

 

 

 

 

 

2015_03_03 

 

 

 

 

 

 

13 

 

-

 

random key per instrument 

Type of telegram 

-

 

Short telegram in conformity to AMR (OMS-
Spec_Vol2_Primary_v301)  

-

 

Long telegram for walk-by read-out 

 
Short telegram (AMR) 

*Factory settings may vary from the above. 

13.3.3

 

Activation of the radio interface  

The radio interface 

leaves the factory deactivated

. It can be activated as follows:  

a)

 

Without using additional software the radio function can be activated by pressing the 
push-button  for  over  3  seconds  while  the  display  is  showing  the  item  ‘M-Bus 
address’,  (see  section  10  “Display”  Level  2/Technician’s  Loop).  The  standard  factory-settings  will  be 
activated.  

b)

 

The radio function can also be activated using the software ’Device Monitor’. This software can be ordered 
separately  as  an  option.  The  exact  procedure  for  activating  the  radio  function  using  this  software  is 
described in the accompanying handbook.  

After successful activation of the radio function a black triangle will appear permanently in the lower left corner of 
the display.  
If using the compact mode, for one hour after activation the meter will transmit in installation mode. This means 
that format telegrams and compact telegrams will be send alternately. During installation mode at least one meter 
of the version being installed (forward or return flow, heat or  cooling or heat/cooling, pulse inputs, display units) 
must be received by the Engelmann Read-out Software. The format of the telegram will be stored locally in the PC 
in an .xml file. After completion of the installation mode only compact telegrams will be transmitted. 

13.4

 

Two additional pulse inputs (optional; only in conjunction with M-Bus or radio) 

With this option, additional instruments with pulse outputs can be read out via M-Bus or radio. 
General information about pulse inputs: 
It  is  important  to  note  that  the  acknowledged  state of  the  art  technology  rules  and  the  relevant  legal  restraints 
(international  and  local;  see  13.4.1  “Relevant  norms,  standards  and  literature  on  the  pulse  inputs”)  are  to  be 
observed. 
The installation has to be performed by authorized, skilled persons. 
If the regulations and the information in the installation and operating instruction manuals are not strictly followed, 
or if the installation is shown to be faulty, any resulting expenses will be charged to the company responsible for 
the installation. 

13.4.1

 

Relevant norms, standards and literature on the pulse inputs 

IEC 60364-4-41 (2005-12) 

Low-voltage electrical installations - Part 4-41: Protection for safety - Protection 
against electric shock 

IEC 60364-4-44 (2007-08) 

Low-voltage electrical installations - Part 4-44: Protection for safety - Protection 
against voltage disturbances and electromagnetic disturbances 

IEC 60364-5-51 (2005-04) 

Electrical installations of buildings - Part 5-51: Selection and erection of 
electrical equipment - Common rules 

IEC 60364-5-54 (2011-03) 

Low-voltage electrical installations - Part 5-54: Selection and erection of 
electrical equipment - Earthing arrangements and protective conductors 

EN 50310 (2010) 

Application of equipotential bonding and earthing in buildings with information 
technology equipment 

EN 1434-2 2007 

Heat Meters — Part 2: Constructional requirements 

 

Содержание microCLIMA ULTRA

Страница 1: ...lations for electrical installations are to be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identific...

Страница 2: ...be implemented at the installation site 4 2 General information on the ow sensor Be careful not to pick up the ow sensor on the plastic housing Always pick up and carry the sensor on the threaded or...

Страница 3: ...9 3 260 12 60 24 180 14 4 5 3 DN25 5 10 200 G 2 20 100 40 130 28 8 8 2 6 300 110 30 9 5 4 Mounting position Cooling meter See section 5 Installation for Cooling Applications Straight pipe sections Non...

Страница 4: ...g System Please inspect and check all dimensions to be sure that there is suf cient space in the intended location for installation of the ow sensor Flush the system thoroughly before installing the o...

Страница 5: ...w The calculator should be mounted on the wall for example Attention must be paid that the cables connected to the calcu lator are laid such that condensation water cannot run along them and into the...

Страница 6: ...lable which makes it possible for the wall mounting support to be mounted using standardized drill holes The centre to centre drill hole separation for the wall mounting unit and direct screw mounting...

Страница 7: ...on Slowly open the shut off valves Check that there are no leaks Check the following points Are all the shut off valves open Is the meter of the right size Is the heating heating cooling system clear...

Страница 8: ...dress factory setting is the serial number 10 Tariff register 1 Value alternating with tariff register no and criteria2 11 Tariff register 2 Values alternating with tariff register no and criteria2 12...

Страница 9: ...to 100 3 to 130 for temperature range 1 to 180 C Temperature difference cooling K 3 to 50 Calculation of heat from K 0 05 Calculation of cooling from K 0 05 Dual purpose heat cooling meter K HC 0 5 Re...

Страница 10: ...lustrations that apply depending on the interface Connection of M Bus Connection of pulse outputs or inputs Connection of pulse outputs heat cooling Connection of power pack Polarity is not important...

Страница 11: ...magnetic disturbances IEC 60364 5 51 2005 04 Electrical installations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical i...

Страница 12: ...tallation boxes substations they must be equipped with non metallic covers or doors The factory setting of the meters clock is standard winter Central European Time GMT 1 There is no automatic changeo...

Страница 13: ...on of the installation mode only compact telegrams will be transmitted 13 4 Two additional pulse inputs optional only in conjunction with M Bus or radio With this option additional instruments with pu...

Страница 14: ...h pulse without unit 1000 litres kWh pulse without unit Installation notes for pulse inputs It is important that the pulse cables are not be affected by or exposed to the M Bus voltage Check the polar...

Страница 15: ...onic switch according to EN 1434 2 2007 Pulse values See chapter 13 5 1 to 13 5 3 Peak switching current 300 mA Switching voltage maximum 35 V Switching power maximum 300 mW Contact isolation 109 Ohm...

Страница 16: ...ed circuited Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable severed sensor cable shorted circuited Int...

Страница 17: ...Directive 2004 108 EC on EMC Directive 2006 95 EC on low voltage Directive 1999 5 EC R TTE The complete signed declaration can be found at www engelmann de 16 Manufacturer Engelmann Sensor GmbH Rudolf...

Отзывы: