Example 3: Display 1234567,8 GJ => pulse value for energy pulse output = 0,1 GJ/pulse
13.5.2
Pulse output for volume (OUT2-Volume)
One pulse is generated by the pulse output for volume when the second-to-last digit of the volume display is
increased by one.
The pulse value is automatically determined by the second-to-last digit of the volume display. The pulse units are
identical to the units of the volume display.
Example 1: Display 12345,678 m
3
=> pulse value for volume pulse output = 0,01 m
3
/pulse
Example 2: Display 12345678 l => pulse value for volume pulse output = 10 l/pulse
13.5.3
Pulse outputs for calculator with combined heat/cooling measurement
For this type of calculator the outputs OUT1 and OUT2 are both outputs for energy.
The behaviour is the same as described in chapter 13.5.1.
OUT1 is the output for the pulses for heat energy.
OUT2 is the output for the pulses for cooling energy.
13.5.4
Technical data pulse output
Pulse output class
OA (electronic switch) according to EN 1434-2:2007
Pulse values
Peak switching current
300 mA ~/-
Switching voltage, maximum
35 V ~/-
Switching power, maximum
300 mW
Contact isolation
> 10
9
Ohm
Contact resistance (on)
max. 25 Ohm
Contact capacity
1.5 pF
Maximum current
120 mA
Withstand voltage (open contact)
350 V ~/-
Closing time
125 ms
Min. close-open-time
125 ms
14
Information Messages
When the instrument has detected an information message, the message symbol is displayed:
The specific message can be found at the menu item 8 ‘Information message’ in Level 1/Main loop (see section 10
“Display”).
The instrument recognizes seven message causes, which can also occur in combination with each other. The
messages are shown on the display. The message code is displayed alternately in binary and hexadecimal form.
Binary display
Description
Hexadecimal display
1 at first place
Checksum fault
H 40
1 at second place
E
2
PROM defective
H 20
1 at third place
Reset
H 10
1 at fourth place
Temperature difference
H 08
1 at fifth place
Internal calibration defective
H 04
1 at sixth place
Return flow sensor defective
H 02
1 at seventh place
Forward flow sensor defective
H 01