background image

 

 

 

 

 

 

2015_03_03 

 

 

 

 

 

 

 

Level 1/Main loop 

 

 

1) Standard display: total 
heat energy; alternating 
display: cooling energy 
(for heating/cooling 
meter)  

 

2) Segment test, all 
segments triggered 
simultaneously 

 

 

3) Heat energy at last 
reading date alternating 
with last reading date

1

 

 

4) Total flow volume in m³ 

 

5) Current power in kW 
 
 
 
 

 

6) Current flow in m³/h 

 

7) Current date 

 

 

8) Information message 
(alternating binary and 
hexadecimal display) 

 

9) Selectable customer-set 
calculator no. (secondary 
address); factory setting is 
the serial number 

 

 

 

 

10) Tariff register 1: Value 
alternating with tariff 
register no. and criteria

2

 

 

 

 

11) Tariff register 2: 
Values alternating with 
tariff register no. and 
criteria

2

 

 

 

12) Momentary reading of 
the pulse counter 1 
alternating with the pulse 
value

2

 

 

 

13) Momentary reading of 
the pulse counter 2 
alternating with the pulse 
value

2

 

 

Level 2/Technician’s loop 

 

1)  Current forward flow 
temperature in °C

 

 

2) Current return flow 
temperature in °C

 

 

3)  Temperature 
difference

 

 

4) Days since first 
verification of calculator

 

 

5) Pulse value of calculator

 

 

6) M-Bus address (primary 
address)

 

 

7) Serial number

 

 

8) Software/firmware 
version

 

 

 

10) Set billing date 

 

 

Содержание microCLIMA ULTRA

Страница 1: ...lations for electrical installations are to be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identific...

Страница 2: ...be implemented at the installation site 4 2 General information on the ow sensor Be careful not to pick up the ow sensor on the plastic housing Always pick up and carry the sensor on the threaded or...

Страница 3: ...9 3 260 12 60 24 180 14 4 5 3 DN25 5 10 200 G 2 20 100 40 130 28 8 8 2 6 300 110 30 9 5 4 Mounting position Cooling meter See section 5 Installation for Cooling Applications Straight pipe sections Non...

Страница 4: ...g System Please inspect and check all dimensions to be sure that there is suf cient space in the intended location for installation of the ow sensor Flush the system thoroughly before installing the o...

Страница 5: ...w The calculator should be mounted on the wall for example Attention must be paid that the cables connected to the calcu lator are laid such that condensation water cannot run along them and into the...

Страница 6: ...lable which makes it possible for the wall mounting support to be mounted using standardized drill holes The centre to centre drill hole separation for the wall mounting unit and direct screw mounting...

Страница 7: ...on Slowly open the shut off valves Check that there are no leaks Check the following points Are all the shut off valves open Is the meter of the right size Is the heating heating cooling system clear...

Страница 8: ...dress factory setting is the serial number 10 Tariff register 1 Value alternating with tariff register no and criteria2 11 Tariff register 2 Values alternating with tariff register no and criteria2 12...

Страница 9: ...to 100 3 to 130 for temperature range 1 to 180 C Temperature difference cooling K 3 to 50 Calculation of heat from K 0 05 Calculation of cooling from K 0 05 Dual purpose heat cooling meter K HC 0 5 Re...

Страница 10: ...lustrations that apply depending on the interface Connection of M Bus Connection of pulse outputs or inputs Connection of pulse outputs heat cooling Connection of power pack Polarity is not important...

Страница 11: ...magnetic disturbances IEC 60364 5 51 2005 04 Electrical installations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical i...

Страница 12: ...tallation boxes substations they must be equipped with non metallic covers or doors The factory setting of the meters clock is standard winter Central European Time GMT 1 There is no automatic changeo...

Страница 13: ...on of the installation mode only compact telegrams will be transmitted 13 4 Two additional pulse inputs optional only in conjunction with M Bus or radio With this option additional instruments with pu...

Страница 14: ...h pulse without unit 1000 litres kWh pulse without unit Installation notes for pulse inputs It is important that the pulse cables are not be affected by or exposed to the M Bus voltage Check the polar...

Страница 15: ...onic switch according to EN 1434 2 2007 Pulse values See chapter 13 5 1 to 13 5 3 Peak switching current 300 mA Switching voltage maximum 35 V Switching power maximum 300 mW Contact isolation 109 Ohm...

Страница 16: ...ed circuited Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable severed sensor cable shorted circuited Int...

Страница 17: ...Directive 2004 108 EC on EMC Directive 2006 95 EC on low voltage Directive 1999 5 EC R TTE The complete signed declaration can be found at www engelmann de 16 Manufacturer Engelmann Sensor GmbH Rudolf...

Отзывы: