Doc. code 1080100090
Version: 2015_03_03
1
Installation and Operating Instructions
Thermal Energy Meter
(Compact Heat Meter, Combined Heat/Cooling Energy Meter)
microCLIMA/SENSOSTAR®2/2+ MSH
Model MSH DE-07-MI004-PTB001 (MID heat)
Model QStar DE-08-MI004-PTB005 (MID heat)
1
Application and Function
Thermal energy meter designed for the measurement of the consumed thermal energy in a closed heating system
or heating / cooling system.
2
Contents of the Package
-
Thermal energy meter consisting of a calculator, a flow sensor and two temperature sensors, connected
permanently
-
Installation kit MSH-SStar, -VStar, -MStar, -AStar or QStar (depending on type)
-
Depending on type of the flow sensor (label):
EAS identification “EN14154” (IST)
EAS identification “EN14154”(TE1)
EAS identification “EN14154” (M60)
EAS identification “EN14154”(A1)
-
Installation and Operating Instructions
3
General Information
-
Valid standards for the application of heat meters: EN 1434, parts 1 – 6; the Measuring Instruments
Directive 2004/22/EC, Annexes I and MI-004, and the relevant national verification regulations.
-
For the selection, installation, commissioning, monitoring and maintenance of the instrument observe the
standard EN 1434 part 6 as well as Annex 22 of the verification regulations (for Germany).
-
National regulations for the consumption measurement of cooling must be observed.
-
The technical regulations for electrical installations must be observed.
-
This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility
(EMC Directive) 2004/108/EC.
-
The identification plate of the instrument and the seals must not be removed or damaged – otherwise the
guarantee and the approved application of the instrument are no longer valid!
-
To achieve measurement stability of the meter it is necessary that the water quality meets the
requirements of the AGFW-recommendation FW-510 and the document VDI (Association of German
Engineers) VDI 2035.
-
The heat meter left the factory in conformance with all applicable safety regulations. All maintenance and
repair work is to be carried out only by qualified and authorized technical personnel.
-
The instrument must be stored and transported at temperatures above-freezing.
-
Instruments with activated radio function are not allowed on air freight.
-
The correct installation point in the system must be chosen: forward or return flow, as stated on the type
identification label.
-
The temperature sensor cables and the cable between the calculator and flow sensor must not be kinked,
rolled up, lengthened or shortened.
-
To clean the heat meter (only if necessary) use a slightly moist cloth.
-
To protect against damage and dirt the heat meter should only be removed from the packaging directly
before installation.
-
If more than one heat meter is installed in one unit, care must be taken to ensure that all the meters have
the same installation conditions.
-
All specifications and instructions listed on the data sheet and in the Application Notes must be adhered
to.