Doc. code 1080100090 

 

 

Version: 2015_03_03 

 

 

 

 

 

4  

Also, please pay attention that the blind hole in the plastic adapter is properly lined up with the metal pin in 
the inside bottom of the EAT on the flow outlet (in rare cases, this pin may not be present: in this case, it is not 
necessary for installation.) 

 

 

4.5

 

Mounting of 

S

ENSO

S

TAR

®

2/2+

 

type MSH-QStar  

-

 

Flush the pipes according to the generally acknowledged rules of technology. Then close all the shut-off 
valves.  

-

 

Open the nearest draining valve for pressure release. 

-

 

Drain the closed-off pipe section. 

-

 

Loosen the coupling rings and remove the old heat meter. 

-

 

Remove all old gaskets. 

-

 

Clean the sealing surfaces. 

-

 

Insert new gaskets. 

-

 

Position the flow sensor correctly, taking into account the direction of flow (arrow on the side of the flow 
sensor)! 

-

 

Tighten the coupling rings. 

-

 

Detach the calculator and mount it, or rotate it to the best position for read-out.  

Note (valid for all types of flow sensors) 

In order  to simplify mounting in narrow  installation spaces  the  compact  meter`s  calculator 
can be detached from the flow sensor.  
To release the calculator pull it carefully up off the flow sensor. 
For heat meter versions it is recommended to detach the calculator. 
For heat/cooling meters the calculator must be detached from the flow sensor. 

5

 

Mounting the Temperature Sensors 

For pipes of sizes < DN25 in new installations (whether new construction or refurbishment) it is required to install 
the temperature sensors directly immersed in the flow (without temperature pockets).  
Note 
During installation of the meter make sure that the temperature sensors are mounted according to their marking. 

5.1

 

Direct mounting (ball valve and T-piece)  

-

 

Remove the blind plug/old temperature sensor and gasket/old O-ring. Clean connection 
surfaces. 

-

 

Slide the O-ring off the temperature sensor and insert it to the bottom of the threaded 
opening of the ball valve or the T-piece. 

-

 

Insert the temperature sensor to at least 15mm, preferably the middle of the ball valve or 
T-piece  (or  a  little  further)  and  screw  tightly.  It  is  important  to  pay  attention  that  the  tip  of  the 
temperature sensor does not touch the bottom (the other side) of the ball valve or T-piece.  

 
 

Plastic adapter: blind hole 

Directional arrows 

Содержание microCLIMA/SENSOSTAR 2 MSH

Страница 1: ...must be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identification plate of the instrument and the...

Страница 2: ...liquid Place the new profile gasket into the connection piece with the flat surface facing up Lubricate the external thread of the flow sensor with a thin layer of food safe silicon grease Check that...

Страница 3: ...then tighten additionally with a suitable wrench to the mechanical end stop metal to metal Detach the calculator and mount it or rotate it to the best position for read out 4 4 Installation of SENSOST...

Страница 4: ...ter s calculator can be detached from the flow sensor To release the calculator pull it carefully up off the flow sensor For heat meter versions it is recommended to detach the calculator For heat coo...

Страница 5: ...ball valves and check installation points for leakage Protect the installation points meter and temperature sensors against manipulation by securing with the seals and sealing wires 6 Start of Operat...

Страница 6: ...ernating display total cooling energy for heating cooling meter 2 Segment test all segments triggered simultaneously 3 Heat energy at last reading date alternating with last reading date1 4 Total flow...

Страница 7: ...2007 class 2 3 Minimum flow qi qp horizontal standard 1 50 vertical Maximum flow qs qp 2 1 Mechanical class M1 Electromagnetic class E1 Protection class of flow sensor IP54 Flow disturbance class UO...

Страница 8: ...he art technology rules and the relevant legal restraints international and local see 9 3 1 Relevant norms standards and literature are to be observed The installation has to be performed by authorize...

Страница 9: ...the unused credit is stored in the instrument and can be used later During M Bus communication with an end instrument the other interfaces push button optical interface of this instrument cannot be us...

Страница 10: ...settings may vary from the above 9 4 3 Activation of the radio interface The radio interface leaves the factory not activated It can be activated as follows a Without using additional software the rad...

Страница 11: ...ns Part 5 54 Selection and erection of electrical equipment Earthing arrangements and protective conductors EN 50310 2010 Application of equipotential bonding and earthing in buildings with informatio...

Страница 12: ...al free pulse output is an electronic switch that outputs counting pulses of the meter which can be used for any purpose The pulse output closes corresponding to the pulse value shown on the type iden...

Страница 13: ...nating total heat and cooling energy with the exception of the hint reset 10 the instrument must be exchanged and sent to the supplier for examination 10 1 Hint description error description Hint Erro...

Страница 14: ...MID Declaration of Conformity For the product described in this document we confirm as the manufacturer that it meets the fundamental requirements of the following directives Directive 2004 22 EC of 3...

Отзывы: