Doc. code 1080100090 

 

 

Version: 2015_03_03 

 

 

 

 

 

3  

-

 

Screw  in  the  heat  meter  tightly  by  hand  and  then  tighten  additionally  with  a  suitable  wrench  to  the 
mechanical end stop (metal-to-metal). 

-

 

Detach the calculator and mount it, or rotate it to the best position for read-out.  

4.3

 

Installation of 

S

ENSO

S

TAR

®

2+

 

type MSH-MStar in a single pipe connection piece (thread M60x1,5) 

The multi-jet flow sensor type MSH-VStar has an external thread M60x1,5 connection as described in EN 14154 
(M60) and must be installed without an adapter in a single pipe connection piece compatible to EN 14154 (M60). 
These pipe connections have no metrological influence on the measurement accuracy. 

Important 
Before installing the flow meter check if the connection piece has the identification EN14154 (M60). If not, the 
label provided with the meter must be applied clearly to the connection piece. 

Mounting: 

-

 

Flush the pipes according to the generally acknowledged rules of technology. Then close all the shut-off 
valves. Open the nearest draining valve for pressure release. 

-

 

Drain the closed-off pipe section. 

-

 

Take into account the direction of flow (connection piece)! 

-

 

Remove the overflow flange or the old heat meter from the connection piece using a wrench. 

-

 

Remove all old gaskets. Check sealing surfaces and threads for imperfections or dirt. If necessary, deburr 
or clean with a suitable cleaning liquid. 

-

 

Place  the  new  profile  gasket  into  the  connection  piece  with  the  flat  surface  facing 
up.  

-

 

Lubricate the external thread of the flow sensor with a thin layer of food safe silicon 
grease. 

-

 

Check that the O-ring on the outlet of the flow sensor is in the correct position. 

-

 

Screw in the heat meter tightly by hand and then tighten additionally with a suitable 
wrench to the mechanical end stop (metal-to-metal). 

-

 

Detach the calculator and mount it, or rotate it to the best position for read-out.  

4.4

 

Installation of 

S

ENSO

S

TAR

®

2+

 

type MSH-AStar in a single pipe connection piece (EAT M77x1,5) 

The multi-jet flow sensor type MSH-AStar has an external thread M77x1,5 connection as described in EN 14154 
(A1) and must  be  installed without  an adapter in a single pipe  connection piece  (EAT)  compatible to EN 14154 
(A1). These pipe connections have no metrological influence on the measurement accuracy. 

Important 
Before installing the flow meter check if the connection piece has the identification EN14154 (A1). If not, the 
label provided with the meter must be applied clearly to the connection piece 

Mounting 

-

 

Flush the pipes according to the generally acknowledged rules of technology. Then close all the shut-off 
valves.  

-

 

Open the nearest draining valve for pressure release. 

-

 

Drain the closed-off pipe section. 

-

 

Take into account the direction of flow (connection piece)! 

-

 

Remove the overflow flange or the old heat meter from the connection piece using a wrench. 

-

 

If a plastic adapter was mounted together with the old meter, it is to remove, too.  

-

 

Check sealing surfaces and threads for imperfections or dirt. If necessary, deburr or clean with a suitable 
cleaning liquid. 

-

 

Lubricate the external thread (M77x1,5) of the flow sensor and the O-ring (66,35x2,62) with a thin layer of 
food safe silicon grease. 

-

 

Screw  in  the  heat  meter  tightly  by  hand  and  then  tighten  additionally  with  a  suitable  wrench  to  the 
mechanical end stop (metal-to-metal). 

-

 

Detach the calculator and mount it, or rotate it to the best position for read-out.  

Attention 
When installing, ensure correct positioning regarding the flow by paying attention to the directional arrows on 
the outer surface of the EAT and on the bottom of the plastic adapter. 

Содержание microCLIMA/SENSOSTAR 2 MSH

Страница 1: ...must be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identification plate of the instrument and the...

Страница 2: ...liquid Place the new profile gasket into the connection piece with the flat surface facing up Lubricate the external thread of the flow sensor with a thin layer of food safe silicon grease Check that...

Страница 3: ...then tighten additionally with a suitable wrench to the mechanical end stop metal to metal Detach the calculator and mount it or rotate it to the best position for read out 4 4 Installation of SENSOST...

Страница 4: ...ter s calculator can be detached from the flow sensor To release the calculator pull it carefully up off the flow sensor For heat meter versions it is recommended to detach the calculator For heat coo...

Страница 5: ...ball valves and check installation points for leakage Protect the installation points meter and temperature sensors against manipulation by securing with the seals and sealing wires 6 Start of Operat...

Страница 6: ...ernating display total cooling energy for heating cooling meter 2 Segment test all segments triggered simultaneously 3 Heat energy at last reading date alternating with last reading date1 4 Total flow...

Страница 7: ...2007 class 2 3 Minimum flow qi qp horizontal standard 1 50 vertical Maximum flow qs qp 2 1 Mechanical class M1 Electromagnetic class E1 Protection class of flow sensor IP54 Flow disturbance class UO...

Страница 8: ...he art technology rules and the relevant legal restraints international and local see 9 3 1 Relevant norms standards and literature are to be observed The installation has to be performed by authorize...

Страница 9: ...the unused credit is stored in the instrument and can be used later During M Bus communication with an end instrument the other interfaces push button optical interface of this instrument cannot be us...

Страница 10: ...settings may vary from the above 9 4 3 Activation of the radio interface The radio interface leaves the factory not activated It can be activated as follows a Without using additional software the rad...

Страница 11: ...ns Part 5 54 Selection and erection of electrical equipment Earthing arrangements and protective conductors EN 50310 2010 Application of equipotential bonding and earthing in buildings with informatio...

Страница 12: ...al free pulse output is an electronic switch that outputs counting pulses of the meter which can be used for any purpose The pulse output closes corresponding to the pulse value shown on the type iden...

Страница 13: ...nating total heat and cooling energy with the exception of the hint reset 10 the instrument must be exchanged and sent to the supplier for examination 10 1 Hint description error description Hint Erro...

Страница 14: ...MID Declaration of Conformity For the product described in this document we confirm as the manufacturer that it meets the fundamental requirements of the following directives Directive 2004 22 EC of 3...

Отзывы: