MACURCO CONTROLLERS & DETECTORS (CONT.) 
 

SETTING THE CONTROLS 

 If your installation has no pre-determined Fan and Alarm set points, Macurco makes the following suggestions:  Set the 
FAN 1 level 50% higher than the average time weighted average of carbon monoxide (CO), usually 50 ppm, that is desired in the 
facility.  This will be a FAN 1 setting of 75. 
 Set the 

SS103-10A

 FAN 2 level 50% higher than FAN 1, or about 112 ppm 

 Set the 

SS103-3A

 FAN 2 and the 

SS103-10A

 ALARM to 200ppm.  Set both Alarm Delays to about 30 minutes. 

 NOTE:  Do not set the 

SS103-10A

 ALARM higher than 200 ppm when using 

SS102HC-1

 sensors. 

 If the Alarm relay is used to operate a fan, Macurco suggests that the Time Delay be set to about 3 minutes, and on the 

SS103-10A

, the ALARM level be set to 50% higher than the FAN 2 or about 170. 

 

ALARM DELAY PROGRAMMING: SS103-10A 

 Set the ALARM adjustment pot to the desired STEL (Short Term Exposure Limit). Usually, this is the Uniform Building 
Code (UBC) standard of 200 ppm.  (OSHA suggests using a 200 ppm CEILING, but currently has no standard for STEL for carbon 
monoxide.)  To set the Alarm delay on the 

SS103-10A

 use the four section programming switch, which is located on the printed 

circuit board near the fan and alarm relays.  A chart inside the cover of the case shows the settings for popular delays.  Figure 1 
shows more settings. 
 
Figure 1. 
ON 
 
OFF 
         1    2   3    4      1    2    3   4      1    2    3   4      1   2    3    4      1    2   3    4      1    2   3   4 
   50 min.      44 min.             35 min.           25 min.               8 min.             15 sec. 
 

NOTE:

  If using 

SS102HC-1

 sensors, do not set the Alarm above 200. 

 

ALARM ACTION 

 If an alarm is used, a procedure should be set up in the facilities emergency response procedures for what action to take 
when the alarm occurs.  Consider the following in making those decisions: 
 The Carbon Monoxide levels of 50 ppm averaged over 8 hours and 200 ppm for some time period, are based on full shift 
exposures of workers.  This usually does not happen in parking garages, where most people are there for only a few minutes. 
 Unless there are full time workers in the facility, Macurco suggests that CO alarms be not considered as life threatening 
emergencies.  Instead use them as advisories to check that all control system components are operating OK. 
 For the 

SS102H

, in addition to Carbon Monoxide, this system will actuate on smoke and various gases such as gasoline 

fumes, propane, alcohol and other combustible vapors. 
 

LIMITED WARRANTY 

 The SS102H, SS102HC-1, SS103-3A, and SS103-10A gas detectors are warranted to be free from defective material and 
workmanship for a period of one (1) year from the date of installation.  If any component becomes defective during the warranty 
period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below.  This warranty 
does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise.  
The above warranty is in lieu of all other express warranties, obligations or liabilities.  THE IMPLIED WARRANTIES OF 
MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF ONE (1) YEAR FROM 
THE PURCHASE DATE.  Macurco shall not be liable for any incidental or consequential damages for breach of this or any other 
warranty express or implied arising out of or related to the use of said gas detector.  Manufacturer or its agent’s liability shall be 
limited to replacement or repair as set forth above.  Buyer’s sole and exclusive remedies are return of the goods and repayment of the 
price, or repair and replacement of non-conforming goods or parts.  (The Uniform Commercial Code applicable in the State of 
Colorado shall govern.) 

RETURN INSTRUCTIONS 

 Call (303) 781-4062 for a Return Authorization number.  Then carefully pack the gas detector with a written description of 
the nature of the return.  Send the unit to the following address: 

Macurco Inc. 

3946 South Mariposa Street 

Содержание SS102HC-1

Страница 1: ... Set up color coding so that the cable will match the same terminals at the sensor and control panel The SS102HC 1 has four pigtail leads two red for power and a white and black for output There is an internal switch in the SS102HC 1 located on the printed circuit board that must be set to volts SS102H SENSOR OPERATION The SS102H sensors have two lights one green and one red The green light is a p...

Страница 2: ...ntroller supplies all power to and receives information from up to ten SS102H or SS102HC 1 Carbon Monoxide Sensors The panel can control three fans or two fans and one alarm circuit Please refer to the Automatic Exhaust Fan Controllers For Parking Garages data sheet for more technical and wiring information SS103 INSTALLATION Mount the SS103 panel in the desired location Knock out SS103 3A or dril...

Страница 3: ...NSOR red light turns on at which time the amber FAN light starts to flash on and off there is a two minute delay before the fan relay is actuated as shown by a continuous FAN light Any of the SENSOR red lights turn on whenever the Fan sensitivity setting is exceeded at any sensors location Should the Carbon Monoxide level continue to rise FAN 2 on the SS103 10A will turn on then the FAN3 ALARM wil...

Страница 4: ...posures of workers This usually does not happen in parking garages where most people are there for only a few minutes Unless there are full time workers in the facility Macurco suggests that CO alarms be not considered as life threatening emergencies Instead use them as advisories to check that all control system components are operating OK For the SS102H in addition to Carbon Monoxide this system...

Страница 5: ...5 Englewood Colorado 80110 WWW MACURCO COM REV 2 99 ...

Отзывы: