background image

 

3

 
MACURCO CONTROLLERS & DETECTORS (CONT.) 

 
SS103 OPERATION 

START-UP 

 Turn the FAN sensitivity level pots to the center of their ranges.  When power is first applied to the 

SS103

, only the Green 

“POWER” light should be on.  If 

SS102HC-1

 sensors are used, the appropriate green SENSOR lights on the 

SS103

 will be on, and 

 
One or more FAN circuits may turn on as the 

SS102HC-1

 goes through its self test cycle, which provides an increasing voltage 

during the warm up cycle.  After one and one half minutes, the 

SS102H

 sensors will complete their warm-ups, and all 

SS102

 

“SENSOR” green lights should be on. (If not all zones are used on the 

SS103-3A &-10A

 only those appropriate green lights will be 

on).  These 

SS103

 green lights show the sensors are on and in normal operation, and that the wiring between the sensor and control 

panel is OK.  The 

SS102HC-1

 has a 2 1/2 minute warm-up cycle, during which the output voltage progressively increases from 1.0 

to 2.1 volts, which will cause the appropriate 

SS103

 zone lights to actuate. 

 Some or all of the Red “SENSOR” lights on the 

SS103-10A

 panel may be on at this time.  These red lights show when a 

sensor output reaches the level of carbon monoxide to actuate FAN1, FAN2 or FAN3/ALARM.  At the same time a SENSOR Red 
light turns on, the amber FAN light or lights start to flash on and off.  If the level of CO is high enough, the Red ALARM light also 
will flash on and off.  Flashing lights indicate that the time delays before relay turn on has been activated. 
 The 

SS103-3A

 has multi-colored lights to show sensor status.  They will be off on zones to which no sensors are connected.  

Normal operation and clean air is shown by a green sensor light.  The light turns amber when “FAN 1” is actuated, then turns red 
when “FAN 2” is exceeded.  The ALARM relay is delayed, by the ALARM DELAY setting, from the FAN 2 level setting. 
 Allow the system to stabilize for 10 or 20 minutes. All SENSOR red lights, the FAN amber lights, and the red ALARM 
lights should be off once the sensors have warmed up, and the air has been cleared out by the fans. 
 

SS103-10A 

 For the 

SS103-10A

, from the time a “SENSOR” red light turns on, at which time the amber FAN light starts to flash on and 

off, there is a two minute delay before the fan relay is actuated, as shown by a continuous FAN light.  Any of the SENSOR red lights 
turn on whenever the Fan sensitivity setting is exceeded at any sensors location.  Should the Carbon Monoxide level continue to rise, 
FAN 2 on the 

SS103-10A

 will turn on, then the FAN3/ALARM will turn on.  At first, the red FAN3/ALARM light flashes on and 

off during the delay period, then turns on steady as the relay closes to actuate the alarm circuit. 
 

SS103-3A 

 The 

SS103-3A 

differs in operation in that it has a shorter delay (30 seconds) FAN on and a short (15 second) FAN turn off 

delay.  Also, the ALARM range is adjustable continuously from 3 to 33 minutes.  This ALARM relay is delayed from the FAN 2 
turn on set point. 
 The unit uses 10Amp field replaceable Autofuses on the three output relay circuits to protect them. 
 

TESTING THE SYSTEM 

 The best way to functionally test the systems is to run a car (the older and smog producing the better) near each sensor and 
observe system operation.  Make sure the 

SS103 

potentiometers are set in reasonable ranges: The Fans between 50 and 150 and the 

Alarm at 200 or less. 
 

SS102H 

 Functionally test the system by introducing Carbon Monoxide gas into each sensor, while watching for each 

SS103

 

SENSOR red light to turn on.  A convenient source of CO is cigarette smoke.  Hold a lighted cigarette under each sensor, for several 
minutes, so the smoke drifts up through the sensor.  Gas from an 

unlit

 butane cigarette lighter can also be used to test the system.  

Shoot the gas into the holes near the lights of the case.  If the job specifications require actual CO testing, the 

SS102HC-1

 sensors 

should be used. 
 

SS102HC-1 

 A switch inside the sensor is labeled TEST.  Pushing this switch once puts the sensor into a 2 1/2 minute test mode where it 
steps from 1.0 to 2.1 volts. This progressive increase in voltage will cause the 

SS103

 control panel to turn on Fan and Alarm relays 

accordingly.  The 

SS102HC-1

 optional Field Calibration Kit (FCK), which includes a cylinder of 50 ppm carbon monoxide gas, can 

be used to test the 

SS102HC-1

 sensors.  If the job requires actual CO testing, other cylinders of gas at other levels can be purchased, 

and used with the FCK. 
 
 

Содержание SS102HC-1

Страница 1: ... Set up color coding so that the cable will match the same terminals at the sensor and control panel The SS102HC 1 has four pigtail leads two red for power and a white and black for output There is an internal switch in the SS102HC 1 located on the printed circuit board that must be set to volts SS102H SENSOR OPERATION The SS102H sensors have two lights one green and one red The green light is a p...

Страница 2: ...ntroller supplies all power to and receives information from up to ten SS102H or SS102HC 1 Carbon Monoxide Sensors The panel can control three fans or two fans and one alarm circuit Please refer to the Automatic Exhaust Fan Controllers For Parking Garages data sheet for more technical and wiring information SS103 INSTALLATION Mount the SS103 panel in the desired location Knock out SS103 3A or dril...

Страница 3: ...NSOR red light turns on at which time the amber FAN light starts to flash on and off there is a two minute delay before the fan relay is actuated as shown by a continuous FAN light Any of the SENSOR red lights turn on whenever the Fan sensitivity setting is exceeded at any sensors location Should the Carbon Monoxide level continue to rise FAN 2 on the SS103 10A will turn on then the FAN3 ALARM wil...

Страница 4: ...posures of workers This usually does not happen in parking garages where most people are there for only a few minutes Unless there are full time workers in the facility Macurco suggests that CO alarms be not considered as life threatening emergencies Instead use them as advisories to check that all control system components are operating OK For the SS102H in addition to Carbon Monoxide this system...

Страница 5: ...5 Englewood Colorado 80110 WWW MACURCO COM REV 2 99 ...

Отзывы: