Macurco MRS-485 Modbus RS-485 Adapter
REV – 1.0
[34-2900-0019-7]
7
|
P a g e
2.4
Specifications
•
Power & Current (without detector): 1.5W (max) from 12 to 24 VAC or VDC.
•
Shipping Weight: 0.25 lb (0.11 kg)
•
Size: 3 1/2 x 2 x 1 3/4 in. (8.9 X 5.1 X 4.4 cm)
•
Operating Environment: 14°F to 122° F (-10°C to +50°C), 20 to 90% RH non-condensing
•
Connections: plugs/terminals
•
Color: Blue
•
Mounting screw and screwdriver included
•
BRS-485 operates as Modbus RTU Slave, BACnet MSTP Server, Metasys N2 Slave or Siemens FLN Slave
•
Baud Rate:
Modbus: 2400, 4800, 9600, 19200 (default), 38400, 57600, 115200 bps
BACnet: 9600, 19200, 38400 (default), 57600, 76800, 115200 bps
Metasys N2 Slave: 9600
Siemens FLN Slave: 2400, 4800, 9600, 19200 (default), 38400, 57600, 115200 bps
•
Parity:
Modbus: Odd, Even (default) and None
BACnet: No Parity
Metasys: No Parity
Siemens: No Parity