Power Wire
All field wiring is completed via modular connectors (provided). After wiring, simply plug the modular
connectors into the matching connectors on the BRS-485. The power connections to the remote mounted
detectors should be size AWG18 (minimum) for short runs. Since Macurco detectors are rated for operation
between 12 and 24 VDC or VAC, the voltage drop between the power supply and the BRS-485 should not be an
issue if the recommended power wire gauge guidelines below are followed. The terminals will accept wire from
16 to 28 AWG. To install a wire, strip back approximately 0.25 in. (6 mm) of insulation and insert the bare wire
into the terminal. Tighten the screw clamp and ensure that the wire cannot be easily pulled from the connector.
Wire gauge
Feet
Meters
18
500
152
16
800
244
14
1250
381
Table 3-1 Power Wire lengths