18
Configuration and Operation
MacroAir AirLynk
© 2019 MacroAir Technologies Toll Free: 866 668-3247 Fax: 909 890-2313 www.macroairfans.com
Rev Date: 071519
PLC
’s Web Configurator
To Select Device Profiles
1.
Connect the PC via the Ethernet Port
•
Connect a CAT5 Ethernet cable (Straight through or Cross-over) from PC to BACnet on
AirLynk panel.
The Default IP Address of PLC is 192.168.1.100, Subnet mask is 255.255.255.0. If the PC
and PLC are on different IP Networks, assign a static IP Address to the PC on the
192.168.1.xxx network.
•
For instructions on how to navigate your operating system to set up an IP address, and
subnet mask contact your system administrator.
2.
Connecting to Web Configurator
•
After Setting your PC to be on the same subnet as the PLC (Instruction 1. Connect to PC),
open a web browser on your PC and enter the IP address of the PLC; the default address
is 192.168.1.100
•
If the IP address of the PLC has been changed by a previous configuration, you will need
to get the assigned IP address from display (Page 12, BACnet IP setup).
3.
Selecting Profiles for Devices Connected to PLC