Excess Cable at Connection Point
With noise being emitted throughout a typical industrial/commercial environment,
extra cable
should not be coiled up
as the coil itself will create noise/interference in the communication
signal. There should be no more than two feet of excess cable at each connection point.
If more than two feet of cable is needed for future relocation of the fan, run the cable up toward
the ceiling and back down in a horseshoe shape.
ALWAYS AVOID SHARP BENDS OF THE CABLE.