background image

 

8

1

0

2

 

s

e

c

i

v

r

e

S

M

2

M

 

©

  

15

Programming 

 

In general, the alarm panels are preconfigured with a template according to the needs of each customer. 

If any changes to the basic configurations are needed you can apply them from the RControl Admin 

Portal 

https://www.m2mservices.com/admin

 by logging with your administrative credentials.  

You can find the alarm panel by its serial number or by account number, IMEI, etc.  

Select the RControl Alarm System, press the right button and choose “RControl Alarm” menu. 

 

General settings of RControl Alarm  

 

Account Number

 – in the field “Account No” you must fill the number with which the panel will report 

to the central monitoring station. The Account No. must be 4-digits long. By default, the alarm panel is 

configured to report with Account No. “0000”. 
 

 

Periodical tests interval

 – in this field you can configure the interval for the periodical test messages 

(in seconds), that the alarm panel will send.  

 

NOTE:

 This interval is different from the interval configured for the supervision of the GPRS connection – 

the “heartbeat interval”. The connection is supervised on every 10 minutes by default whereas the 

periodical tests are usually sent every couple of hours (e.g. 12 or 24 hours).   
 

 

Configuring a delay in case of mains power outage

 –

 

in the field “Delay”, section “Main Power” 

you can configure the delay (in seconds) after which the device will report the mains power outage.  
 

 

Configuring the Battery level thresholds -

 In section” Battery”, field “Battery low” you can set a low 

voltage threshold, under which the alarm panel will send “Low Battery” event. In the filed “Battery 

Critical Low” you can set even lower voltage threshold and if the battery voltage goes under this level, 

it will be considered as critically low.  

  

To preserve the battery from permanent damage, you can configure the panel to shut down automatically 
if the voltage of the battery drops under the critically low threshold. You can enable that feature by 
checking the “Auto shutdown when battery critical low” checkbox.  

Configuring the partitions  

The RControl Alarm panel supports 2 Partitions.  

 

You can configure different Partition settings from RControl Alarm menu, section “Partitions”:  

 

Partition name – 

the name which will be visible in the mobile application.

 

 

 

Entry time 

(in seconds) – the interval, after which an alarm will be sent to the monitoring station, if no 

valid user code is entered. 

 

Exit time 

(in seconds) – the time interval from the physical arming from a user and the arming of the 

alarm panel. You can choose when the Exit time will be applied – when arming from a wireless 

keyfob, in case of remote arming from the mobile application or both.

 

 

 

Alarm cycle duration 

(in seconds) – the time interval when the siren will be active after an alarm 

event

.

 

 

Sound indication from the siren 

in case of tamper alarm

.

 

Содержание RControl-LA

Страница 1: ...M2M Services Ltd 1 Kukush Str building M8 Sofia 1309 Bulgaria www m2mservices com RControl LA Smart Hybrid Alarm System Installation and Programming Guide Doc No 04003 V1 0 10 2018...

Страница 2: ...keyfobs 11 Labelling the keyfobs 11 Con guring the panic button of the keyfob 11 Wireless detectors 12 Pairing a wireless detector 12 Disabling a wireless detector 13 Deleting a wireless detector 13...

Страница 3: ...o its intended purpose and does not cover damage to the Device caused by installation or removal of the Device or any of its components This warranty is voided if the Device has been damaged by improp...

Страница 4: ...ust be done only by qualified safety aware personnel Don t disassemble or refit the Device Do not attempt to personally repair it Main powers must be disconnected before any installation or tuning wor...

Страница 5: ...artition control panel with the following features Built in GPRS communicator Remote control via Smartphone 2 Partitions 8 Wired zones 16 with zone doubling 32 Wireless zones Supports up to 16 keyfobs...

Страница 6: ...output 200 mA Power Requirements Battery 12 V 2 6 Ah minimum rechargeable sealed lead battery Digital Communicator Specification Built in digital communicator Frequency Dual band UMTS HSPA 850 1900 MH...

Страница 7: ...choose location that is below ground level as this can impair wireless reception Do not choose location that can be easily viewed from outside the premises The Control Panel should be mounted on the w...

Страница 8: ...te FCC regulations Keypad Mount the keypad where it is accessible in a dry and secure location Perform the following steps to mount the keypad Remove the keypad front plate by inserting a screwdriver...

Страница 9: ...the alarm panel Battery Plug the battery connector into the connector on the control panel s circuit board Plug the red cable to the of the battery and the blue one to the of the battery Ensure the ba...

Страница 10: ...take which will not allow you to pair the next keyfobs before you disarm the panel The learning mode lasts 30 seconds If the receiver does not receive signal from the keyfob in the timeframe of 30 sec...

Страница 11: ...e for each keyfob Labelling the keyfobs Each keyfob reports with different user number in the range between 101 116 When pairing the keyfobs they automatically receive labels Keyfob 101 Keyfob 116 The...

Страница 12: ...beep once and the red PAIR LED will turn off The siren will beep four times if there was an error during the pairing When a new detector is successfully paired the panel reports an event Module Added...

Страница 13: ...all keyfobs and wireless detectors NOTE This procedure will delete all paired keyfobs and wireless detectors To pair the keyfobs and the wireless detectors again you should repeat the pairing procedu...

Страница 14: ...tor as many times as required until the panel recognizes the sensor When the sensor is successfully enrolled the panel will beep once and the red PAIR LED will turn off The siren will beep four times...

Страница 15: ...wer you can configure the delay in seconds after which the device will report the mains power outage Configuring the Battery level thresholds In section Battery field Battery low you can set a low vol...

Страница 16: ...en the alarm cycle time expires the zone restore event will be reported only when the zone is really restored In addition even when there was a restore during the alarm cycle this restore will not be...

Страница 17: ...h prevent the panel from arming Follow STAY zone This is a Follow zone that is not monitored when the panel is partially armed STAY Arm Instant STAY zone This is an Instant zone that is not monitored...

Страница 18: ...pressed 24 Hours Flood When this zone is violated the panel will immediately latch the alarm output and communicate to the central station The alarm will sound until the alarm cycle duration expires o...

Страница 19: ...is strongly recommended that the end user changes the User name and Password and provides an email for password recovery Remote Arming Disarming via the RControl Application To enable the remote contr...

Страница 20: ...exit the System Test mode and indicate this with a sound The programming icon will also be off If some of the sensors is not activated the system will not generate a sound indication for exiting a te...

Страница 21: ...8 1 0 2 s e c i v r e S M 2 M 1 2 Zone problems Wiring Configuration Faulty detectors Siren not working Check wiring Programming AUX overcurrent...

Отзывы: